2021-05-13 11:29:04 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 21041043 |
| 5/13/2021 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROVIDE PLUMBING FIXTURE CALCULATIONS IN ACCORDANCE |
| WITH TABLE 403.1 FBC P. PROVIDE A SCHEDULE INDICATING |
| THE REQUIRED AND PROVIDED NUMBER OF FIXTURES. PLEASE |
| NOTE THAT A DRINKING FOUNTAIN IS A REQUIRED PLUMBING |
| FIXTURE FOR AN ASSEMBLY OCCUPANCY UNLESS THE EXCEPTION |
| UNDER SECTION 410.4 SUBSTITUTION IS CLAIMED: WHERE |
| RESTAURANTS PROVIDE DRINKING WATER IN A CONTAINER FREE |
| OF CHARGE, DRINKING FOUNTAINS SHALL NOT BE REQUIRED IN |
| THOSE RESTAURANTS. IF THIS IS THE INTENTION, PLEASE |
| PLACE A NOTE ON THE CALCULATION SCHEDULE. |
| |
| 2) SHEET A2.1.1: PROVIDE THE KNEE AND TOE CLEARANCES |
| FOR THE SINKS- SECTIONS 606.2 & 306.1 FBC ACC. |
| |
| 3) SHEETS P0.1, P2.1, & P5.1: PROVIDE AN EQUIPMENT |
| SCHEDULE AND SUBMIT MANUFACTURER'S SPECIFICATIONS FOR |
| THE NEW GREASE INTERCEPTOR- SECTION 1003.3.5 FBC P. |
| |
| A) PROVIDE INTERCEPTOR SIZING CALCULATIONS. |
| |
| B) THE DRAINAGE FROM THE HAND SINK AND FLOOR DRAINS IN |
| THE SERVING AREA SHALL NOT DRAIN INTO THE GREASE |
| INTERCEPTOR- SECTION 1003.3.1 FBC P. THE HAND SINK IS |
| NOT CONSIDERED A SIGNIFICANT GREASE WASTE CONTRIBUTOR, |
| AND THE FLOOR DRAINS IN THE SERVING AREA ARE DRAINING |
| CLEAR WATER WASTE. |
| |
| C) PROVIDE A SAMPLING PORT DETAIL FOR THE INTERCEPTOR- |
| SECTION 1003.3.5 FBC P. |
| |
| D) PROVIDE A SITE AND SURVEY PLAN SHOWING THE LOCATION |
| OF THE NEW GREASE INTERCEPTOR. IF TO BE INSTALLED IN A |
| PARKING LOT OR DRIVE AREA, A HEAVY-DUTY TRAFFIC LID |
| WILL BE REQUIRED- SECTION 107.2.1 WPB AND 1003.3.5 FBC |
| P. |
| |
| 4) PROVIDE AN INDIRECT WASTE DETAIL FOR THE |
| 3-COMPARTMENT SINK- SECTION 802.1.1 FBC P. |
| |
| 5) P2.1: NONCOMPLIANT SANITARY WET VENT- TWO WATER |
| CLOSETS UPSTREAM OF THE DRY VENT CONNECTION- SECTION |
| 912.2.1 FBC P. |
| |
| 6) P0.1: PROVIDE THE EFFICIENCY RATING OF THE TANKLESS |
| WATER HEATER- TABLE C404.2 FBC EC. |
| |
| 7) P0.1, P3.1, & P5.1: PROVIDE EITHER A RECIRCULATION |
| PUMP FOR THE HOT WATER SYSTEM OR POINT OF USE WATER |
| HEATERS AT THE LAVATORIES- SECTION AND TABLE C404.5.1 |
| FBC EC. |
| |
| 8) P3.1: PROVIDE THE TEXT FOR KEYNOTES 1 & 2- SECTION |
| 107.2.1 WPB. |
| |
| 9) P5.1: KEY NOTES #1 & 3 SPECIFY CIVIL PLANS FOR |
| LOCATIONS OF THE SEWER LATERAL, AND NEW WATER METER AND |
| BACKFLOW PREVENTER. PLEASE PROVIDE THE PLANS- SECTION |
| 107.2.1. PLEASE NOTE THAT A SEPARATE PERMIT IS REQUIRED |
| FOR INSTALLATION OF THE POTABLE WATER SERVICE BACKFLOW |
| ASSEMBLY- A FL. LICENSED PLUMBING CONTRACTOR SHALL |
| OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE |
| BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB |
| AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL |
| BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |