Plan Review Notes For Permit 21041043 |
Permit Number |
21041043 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-05-13 12:05:09 | 1ST REVIEW FBC-2020 FUEL GAS | | PERMIT- 21041043 | | 5/13/2021 | | | | CODES IN EFFECT: | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET P5.1: LIST THE 2 PSI PIPE SIZING TABLE | | 402.4(5) FBC FG. | | | | 2) P5.1: PROVIDE THE BRANCH PIPE SIZES TO THE COOKING | | APPLIANCES- TABLE 402.4(2) FBC FG. | | | | 3) P5.1: SHOW THE LOCATIONS OF REQUIRED PIPE UNIONS AT | | THE REGULATORS- SECTION 410.2&7) FBC FG. | | | | 4) P5.1: PROVIDE COMBUSTION AIR CALCULATIONS AND | | INDICATE HOW THE AIR WILL BE PROVIDED- SECTION 304.1 | | FBC FG. | | | | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE COOKING | | APPLIANCES AND WATER HEATER- SECTIONS 623.1 AND 624.1 | | FBC FG. DEFERRED SUBMITTALS ARE ACCEPTABLE PER SECTION | | 107.3.4.1 WPB. | | | | 6) SUBMIT REGULATOR SPECS MARKED UP OR HIGHLIGHTED TO | | SHOW INLET AND OUTLET PRESSURES AND PIPE SIZES- SECTION | | 410.2 FBC FG. DEFERRED SUBMITTALS ARE ACCEPTABLE- | | SECTION 107.3.4.1 WPB. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | CCOLE@WPB | | |
|