2021-05-14 15:30:37 | CODES IN EFFECT | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 | | 7TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW: | | | | 1) PANEL SCHEDULE AND POWER PLAN DO NOT MATCH. SOME | | CIRCUITS ON PANEL SCHEDULE (A-14. A-4) ARE NOT SHOWN ON | | POWER PLAN | | AND SOME CIRCUITS ON POWER PLAN (A-26) ARE NOT SHOWN ON | | PANEL SCHEDULE. POWER PLAN SHOWS TWO CIRCUITS A-23 | | CONNECTED TO RECEPTACLES | | BUT SPACE 23 IS ALREADY ALLOCATED FOR CONDENSER UNIT 1. | | PLEASE CORRECT DISCREPANCIES AND SUBMIT NEW POWER PLAN | | AND PANEL SCHEDULES. | | | | ENRIQUE QUINONEZ PE | | ELECTRICAL PLANS EXAMINER | | DEVELOPMENT SERVICES | | CITY OF WEST PAM BEACH | | 401 CLEMATIS STREET, 1ST FLOOR | | WEST PALM BEACH, FL 33401 | | | | FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS, | | 561-805-6746. | | |
|