Plan Review Notes For Permit 21040975 |
Permit Number |
21040975 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-04-29 16:36:36 | BATH REMODEL | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected]. | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) PLEASE SHOW THE SHOWER WALL FINISHES TO COMPLY WITH | | FBC 1210.2.3 SHOWERS. | | SHOWER COMPARTMENTS AND WALLS ABOVE BATHTUBS WITH | | INSTALLED SHOWER HEADS SHALL BE FINISHED WITH A SMOOTH, | | NONABSORBENT SURFACE TO A HEIGHT NOT LESS THAN 72 | | INCHES (1829 MM) ABOVE THE DRAIN INLET. |
|