2021-04-21 13:41:04 | 04/21/21 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF |
| THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH |
| FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA |
| STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC. |
| 107.1 GENERAL. |
| |
| 2. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| 3. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER THE 2020 FBC RES. SEC. G2413.2. WHAT IS |
| THE LONGEST LENGTH? |
| |
| 4. THE PLANS INDICATE AN EXISTING GAS METER. THE BTU |
| LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED TO THE |
| TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING |
| SYSTEM IS APPROPRIATELY SIZED. IF UNDERSIZED, THE |
| EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE |
| OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM |
| THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD |
| OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO |
| EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH |
| OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE |
| EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE |
| SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE |
| REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES |
| PER THE 2020 FBC RES. SECS. G2412.4, G2412.8, G2413.1, |
| G2413.2, G2413.3. LIST THE BTU LOAD OF EACH APPLIANCE |
| AND THE TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2020 |
| FBC RES. SEC. G2413. |
| |
| 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2020 |
| FBC RES. SEC. G2407.1 AND G2439.4 (CLOTHES DRYERS). |
| |
| 6. SUBMIT MANUFACTURER?S SPECIFICATION |
| SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH 2020 FBC RES. SEC. G2408.1. |
| |
| 7. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2020 |
| FBC RES. SEC. G2413.2 AND G2404.3. |
| |
| 8. SUBMIT A SIZING TABLE USED IN THE DESIGN FOR THE GAS |
| SYSTEM OR PLACE A NOTE ON BOTH SETS OF PLANS LISTING |
| THE SIZING TABLES FROM GAS CODES OR ANOTHER STANDARD |
| USED IN THE DESIGN OF THIS SYSTEM PER THE 2020 FBC RES. |
| SEC. G2413.3. |
| |
| 9. PLEASE SUBMIT THE MANUFACTURER?S SPECIFICATIONS FOR |
| THE PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| BUILDING'S EXTERIOR SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION PER THE 2020 FBC RES. SEC. G2421.1. |
| |
| 10. PLEASE SHOW AND LABEL ALL UNIONS IN FRONT OF |
| REGULATOR 1? OF EITHER SIDE PER THE 2020 FBC RES. SEC |
| G2421.2. |
| |
| 11. PLEASE LABEL THE SHUT-OFF VALVE ON GAS ISOMERIC PER |
| THE 2020 FBC RES. SEC. G2401.1.3. |
| |
| 12. SHOW DRIP LEG ON EQUIPMENT INSTALLED, EXCEPT FOR |
| APPLIANCES, RANGE, DRYERS & OD GRILLS PER THE 2020 FBC |
| RES. SEC. G2419.2. |
| |
| 13. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON |
| THE APPLICATION. PLEASE PROVIDE A BONA FIDE SIGNED |
| CONTRACT PER THE WPB AMENDMENTS TO THE FBC 109.3. |
| BUILDING PERMITS VALUATIONS. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |