Plan Review Notes
Plan Review Notes For Permit 21040895
Permit Number 21040895
Review Stop B
Sequence Number 1
Notes
Date Text
2021-04-27 10:34:22JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY, THURSDAY & FRIDAY 7:00 AM TO 3:00
 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. PROVIDE THE FOLLOWING INFORMATION FOR MIAMI-DADE NOA
 NO.: 20-0723.29 FOR THE PROPOSED FLAT ROOF SYSTEM TO BE
 USED CORRESPONDING TO ENGINEERS CALCULATIONS. COVER
 PAGE, EVALUATION REPORTS, LIMITATIONS PAGE AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL25621.02-R2 IS NOT RATED FOR USE IN ZONE 1,
 2 OR 3 FOR STRUCTURES LOCATED IN EXPOSURE D, WITH FLAT
 ROOF LESS THAN 7 DEGREES, HIP ROOF WITH MAX SLOPE OF
 12:12 OR GABLE ROOF WITH SLOPE BETWEEN 4.4:12 & 12:12
 12:12 WITH A MEAN ROOF HEIGHT 30 FEET OR LESS WIND
 SPEED 170 MPH. PROVIDE SIGNED AND SEALED ENGINEERING
 FOR USE OR SELECT A SYSTEM THAT MEETS THE ABOVE
 CRITERIA.
  