2021-11-02 17:02:23 | RESIDENTIAL (R3) ADDITION, THIRD BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #21040876 |
| |
| ORIGINAL COMMENT: |
| 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 1106 |
| FBC-EXISTING BUILDING AND SEC. R101.5 FBC-ENERGY |
| CONSERVATION. |
| NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL |
| REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID |
| CONFLICTS/DELAYS. |
| |
| A)THE ENERGY FORM R405-2020 IS REQUIRED TO BE SIGNED |
| AND DATED BY THE OWNER, ARCHITECT OR OWNER'S LEGALLY |
| DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS |
| REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, |
| PRIOR TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. REVISED FORM WAS NOT |
| SUBMITTED. |
| |
| B)THERE ARE TWO DIFFERENT ENERGY CALCULATIONS |
| SUBMITTED. ONE IS FORM 405-2020 PREPARED BY M. ABBOTT |
| AND FORM R402-2020 PREPARED BY THE ARCHITECT. |
| INFORMATION ON FORM R402-2020 DOESN'T MEET THE MINIMUM |
| PRESCRIPTIVE REQUIREMENTS FOR THE GLAZED FENESTRATION |
| (SHGC) AND THE A/C UNIT CAN NOT BE INSTALLED IN THE |
| ATTIC. THIS FORM CAN NOT BE USED. PLEASE REMOVE THIS |
| FORM. |
| USE FORM R405-2020 AND MAKE SURE IS SIGNED BY THE OWNER |
| OR ARCHITECT TO AVOID CONFLICTS/DELAYS. |
| SEC. R103.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. REVISED FORM WAS NOT |
| SUBMITTED. |
| |
| C) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING THE BUILDER'S NAME, JURISDICTION NUMBER (THIS |
| IS JURISDICTION #604700). SEC. R101.5.1.1.2 FBC- ENERGY |
| CONSERVATION. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. REVISED FORM WAS NOT |
| SUBMITTED. |
| |
| D) |
| E) |
| |
| E)DOOR INFORMATION SHOWS A 1FT X 5FT DOOR ON THE SOUTH |
| SIDE. PLANS DON'T SHOW THIS DOOR. WHERE IS THIS DOOR |
| LOCATED AT?. REVISE AS REQUIRED. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. REVISED FORM WAS NOT |
| SUBMITTED. |
| |
| F)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE |
| LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY |
| CONSERVATION. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. REVISED FORM WAS NOT |
| SUBMITTED. |
| |
| NOTE: |
| WHEN RESUBMITTING, PLEASE SEPARATE THE ENERGY |
| CALCULATIONS FROM THE A/C LOAD CALCULATIONS AND ANY |
| OTHER A/C RELATED INFORMATION. A/C PLAN TO BE SUBMITTED |
| UNDER THE DRAWINGS FOLDER. |
| |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| TO AVOID MORE DELAYS, PLEASE FEEL FREE TO CONTACT ME IF |
| YOU HAVE ANY QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |