2021-08-12 18:19:17 | RESIDENTIAL (R3) ADDITION, SECOND BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #21040876 |
| |
| ORIGINAL COMMENT: |
| 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 1106 |
| FBC-EXISTING BUILDING AND SEC. R101.5 FBC-ENERGY |
| CONSERVATION. |
| NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL |
| REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID |
| CONFLICTS/DELAYS. |
| |
| RESPONSE: |
| A)THE ENERGY FORM R405-2020 IS REQUIRED TO BE SIGNED |
| AND DATED BY THE OWNER, ARCHITECT OR OWNER?S LEGALLY |
| DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS |
| REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, |
| PRIOR TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION. |
| |
| B)THERE ARE TWO DIFFERENT ENERGY CALCULATIONS |
| SUBMITTED. ONE IS FORM 405-2020 PREPARED BY M. ABBOTT |
| AND FORM R402-2020 PREPARED BY THE ARCHITECT. |
| INFORMATION ON FORM R402-2020 DOESN'T MEET THE MINIMUM |
| PRESCRIPTIVE REQUIREMENTS FOR THE GLAZED FENESTRATION |
| (SHGC) AND THE A/C UNIT CAN NOT BE INSTALLED IN THE |
| ATTIC. THIS FORM CAN NOT BE USED. PLEASE REMOVE THIS |
| FORM. |
| USE FORM R405-2020 AND MAKE SURE IS SIGNED BY THE OWNER |
| OR ARCHITECT TO AVOID CONFLICTS/DELAYS. |
| SEC. R103.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| C) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING THE BUILDER'S NAME, JURISDICTION NUMBER (THIS |
| IS JURISDICTION #604700). SEC. R101.5.1.1.2 FBC- ENERGY |
| CONSERVATION. |
| |
| D)PROVIDE CORRECT INFORMATION FOR ITEM #2. THE QUESTION |
| ON THIS ITEM IS SINGLE FAMILY OR MULTIPLE FAMILY?. |
| "DETACHED IS NOT THE ANSWER. REVISE AS REQUIRED. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| E) COORDINATE ATTIC INSULATION AND ATTIC VENTILATION |
| WITH ARCHITECT'S PLANS. THESE ITEMS WILL NEED TO BE |
| REVISED BY THE ARCHITECT. SEE ITEMS #2(B) AND #7(D) |
| BELOW. |
| |
| E)DOOR INFORMATION SHOWS A 1FT X 5FT DOOR ON THE SOUTH |
| SIDE. PLANS DON'T SHOW THIS DOOR. WHERE IS THIS DOOR |
| LOCATED AT?. REVISE AS REQUIRED. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| F)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE |
| LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY |
| CONSERVATION. |
| |
| |
| ORIGINAL COMMENT: |
| 2- PROVIDE COMPLETE ROOF FRAMING PLAN FOR THE ADDITION. |
| CLEARLY SPECIFY ALL FRAMING MEMBERS AND CONNECTORS. |
| ALSO, CLEARLY SPECIFY CONNECTION TO EXISTING. |
| SEC. R301.2.1 FBC-RESIDENTIAL. |
| NOTE: TYPICAL WALL SECTION ON SHEET A-3 SPECIFIES ROOF |
| TRUSSES. IT IS NOT CLEAR HOW TRUSSES ARE BUILT IF ONLY |
| TOP CHORD IS SHOWN. COORDINATE WITH ITEM #6 BELOW. |
| REVISE/CLARIFY. |
| |
| RESPONSE: |
| FRAMING OF THE NEW ROOF CORNERS IS NOT CLEAR. ROOF |
| FRAMING PLAN ON SHEET S-1 SHOW THE STRUCTURAL ROOF |
| FRAMING MEMBERS BEING SPACED MORE THAN 24" O.C. AND IT |
| LOOKS LIKE THE CORNER IS NOT PROPERLY FRAMED TO SUPPORT |
| THE REQUIRED LOADS, SPECIALLY AT THE CANTILEVERED ROOF |
| AREA ON THE NORTH CORNER OF THE ROOF. PROVIDE COMPLETE |
| FRAMING DETAIL/SPECIFICATIONS FOR BOTH CORNERS. SPECIFY |
| ALL FRAMING MEMBERS AND CONNECTORS AT ALL ENDS. SEC. |
| R301.1 FBC-RESIDENTIAL AND SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| B)BASED ON THE ROOF FRAMING PLAN ON SHEET S-1 AND THE |
| TYPICAL WALL SECTION ON SHEET A-3, IT LOOKS LIKE THE |
| INTENTION OF THE ARCHITECT IS TO DESIGN AN UNVENTED |
| ATTIC. ARCHITECT TO PROVIDE COMPLETE SPECIFICATIONS |
| SHOWING COMPLIANCE WITH SEC. R806.5 FBC-RESIDENTIAL FOR |
| UNVENTED ATTIC AND UNVENTED ENCLOSED RAFTER ASSEMBLIES. |
| TYPICALLY, THIS IS DONE USING FOAM INSULATION. |
| NOTE: IF SPECIFYING FOAM INSULATION, THEN PROVIDE ICC |
| EVALUATION REPORT REVIEWED BY THE ARCHITECT OF RECORD |
| PRIOR TO SUBMITTAL. |
| NOTE: COORDINATE WITH ITEM #7(D) BELOW. |
| |
| 3- OK |
| 4- OK |
| |
| ORIGINAL COMMENT: |
| 5-PROVIDE COMPLETE WIND DESIGN CRITERIA. SEC. R301.2.1 |
| FBC-RESIDENTIAL. |
| SPECIFY BUILDING EXPOSURE, ULTIMATE AND NOMINAL WIND |
| SPEED. |
| |
| 6- OK |
| |
| ORIGINAL COMMENT: |
| 7- TYPICAL WALL SECTION ON SHEET A-3: |
| A)PROVIDE SPECIFICATIONS CLEARLY SHOWING HOW COMPLYING |
| WITH THE NEW 2020 CODE REQUIREMENT FOR ROOFING |
| UNDERLAYMENT. SEC. R905.1.1.1 FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| PROVIDE PRODUCT APPROVAL OF PEEL AND STICK UNDERLAYMENT |
| SPECIFIED BY THE ARCHITECT. NOTE: PEEL AND STICK |
| UNDERLAYMENT SHALL BE APPROVED FOR SHINGLES OVER 30# |
| ASPHALT FELT AS SPECIFIED BY THE ARCHITECT. |
| |
| B)OK |
| C)OK |
| |
| D)WALL SECTION SPECIFIES R-30 CEILING INSULATION. |
| CLEARLY SPECIFY WHAT TYPE OF INSULATIONS IS PROPOSED. |
| BUTT INSULATION OR FOAM INSULATION. ALSO, IT IS NOT |
| CLEAR IF R-30 INSULATION WILL FIT IN THIS CEILING AREA. |
| VERIFY AS REQUIRED. WALL SECTION SHOWS ROOF RAFTERS BUT |
| IT SPECIFIES ROOF TRUSSES. COORDINATE WITH ITEM #2 |
| ABOVE. |
| NOTE: IF SPECIFYING FOAM INSULATION, THEN PROVIDE ICC |
| EVALUATION REPORT REVIEWED BY THE ARCHITECT OF RECORD |
| PRIOR TO SUBMITTAL. |
| |
| RESPONSE: |
| BASED ON THE ROOF FRAMING PLAN ON SHEET S-1 AND THE |
| TYPICAL WALL SECTION ON SHEET A-3, IT LOOKS LIKE THE |
| INTENTION OF THE ARCHITECT IS TO DESIGN AN UNVENTED |
| ATTIC. ARCHITECT TO PROVIDE COMPLETE SPECIFICATIONS |
| SHOWING COMPLIANCE WITH SEC. R806.5 FBC-RESIDENTIAL FOR |
| UNVENTED ATTIC AND UNVENTED ENCLOSED RAFTER ASSEMBLIES. |
| TYPICALLY, THIS IS DONE USING FOAM INSULATION. REVISE |
| AS REQUIRED AND REVISE INSULATION R-VALUE ACCORDINGLY. |
| |
| NOTE: IF SPECIFYING FOAM INSULATION, THEN PROVIDE ICC |
| EVALUATION REPORT REVIEWED BY THE ARCHITECT OF RECORD |
| PRIOR TO SUBMITTAL. |
| |
| E) OK |
| |
| F)WALL SECTION SPECIFIES SOFFIT VENTS AT 96" O.C. |
| SOFFIT NEEDS CROSS VENTILATION AS REQUIRED BY SEC. |
| R806.1 FBC-RESIDENTIAL. WALL SECTIONS SHOWS ROOF |
| RAFTERS. ROOF RAFTERS DON'T PROVIDE CROSS VENTILATION |
| WHEN THE VENTS ARE SPACED AT 96" O.C. THIS NEED TO BE |
| COORDINATED WITH ITEM #2 ABOVE AND REVISE WALL SECTION |
| SPECIFICATIONS AS REQUIRED. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| RESPONSE: |
| COORDINATE WITH ITEM #7(D) ABOVE. |
| |
| ORIGINAL COMMENT: |
| 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| 61G20-3.001 FOR |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO |
| INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT |
| APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL): |
| |
| A)ROOF SHINGLES. |
| |
| RESPONSE: |
| NOA 20-0318.05 SUBMITTED IS ONLY FOR THE RIDGE CAP |
| SHINGLES. NEED TO PROVIDE THE PRODUCT APPROVAL FOR TH |
| SHINGLES ALSO. |
| |
| B)PEEL AND STICK UNDERLAYMENT SPECIFIED BY THE |
| ARCHITECT. NOTE: PEEL AND STICK UNDERLAYMENT SHALL BE |
| APPROVED FOR SHINGLES OVER 30# ASPHALT FELT AS |
| SPECIFIED BY THE ARCHITECT. |
| |
| 9- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| TO AVOID MORE DELAYS, PLEASE FEEL FREE TO CONTACT ME IF |
| YOU HAVE ANY QUESTIONS REGARDING THESE COMMENTS, |