2021-08-12 18:19:17RESIDENTIAL (R3) ADDITION, SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21040876
  
 ORIGINAL COMMENT:
 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 1106
 FBC-EXISTING BUILDING AND SEC. R101.5 FBC-ENERGY
 CONSERVATION.
 NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 RESPONSE:
 A)THE ENERGY FORM R405-2020 IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER, ARCHITECT OR OWNER?S LEGALLY
 DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 PRIOR TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION.
  
 B)THERE ARE TWO DIFFERENT ENERGY CALCULATIONS
 SUBMITTED. ONE IS FORM 405-2020 PREPARED BY M. ABBOTT
 AND FORM R402-2020 PREPARED BY THE ARCHITECT.
 INFORMATION ON FORM R402-2020 DOESN'T MEET THE MINIMUM
 PRESCRIPTIVE REQUIREMENTS FOR THE GLAZED FENESTRATION
 (SHGC) AND THE A/C UNIT CAN NOT BE INSTALLED IN THE
 ATTIC. THIS FORM CAN NOT BE USED. PLEASE REMOVE THIS
 FORM.
 USE FORM R405-2020 AND MAKE SURE IS SIGNED BY THE OWNER
 OR ARCHITECT TO AVOID CONFLICTS/DELAYS.
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 C) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER'S NAME, JURISDICTION NUMBER (THIS
 IS JURISDICTION #604700). SEC. R101.5.1.1.2 FBC- ENERGY
 CONSERVATION.
  
 D)PROVIDE CORRECT INFORMATION FOR ITEM #2. THE QUESTION
 ON THIS ITEM IS SINGLE FAMILY OR MULTIPLE FAMILY?.
 "DETACHED IS NOT THE ANSWER. REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E) COORDINATE ATTIC INSULATION AND ATTIC VENTILATION
 WITH ARCHITECT'S PLANS. THESE ITEMS WILL NEED TO BE
 REVISED BY THE ARCHITECT. SEE ITEMS #2(B) AND #7(D)
 BELOW.
  
 E)DOOR INFORMATION SHOWS A 1FT X 5FT DOOR ON THE SOUTH
 SIDE. PLANS DON'T SHOW THIS DOOR. WHERE IS THIS DOOR
 LOCATED AT?. REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 F)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
  
 ORIGINAL COMMENT:
 2- PROVIDE COMPLETE ROOF FRAMING PLAN FOR THE ADDITION.
 CLEARLY SPECIFY ALL FRAMING MEMBERS AND CONNECTORS.
 ALSO, CLEARLY SPECIFY CONNECTION TO EXISTING.
 SEC. R301.2.1 FBC-RESIDENTIAL.
 NOTE: TYPICAL WALL SECTION ON SHEET A-3 SPECIFIES ROOF
 TRUSSES. IT IS NOT CLEAR HOW TRUSSES ARE BUILT IF ONLY
 TOP CHORD IS SHOWN. COORDINATE WITH ITEM #6 BELOW.
 REVISE/CLARIFY.
  
 RESPONSE:
 FRAMING OF THE NEW ROOF CORNERS IS NOT CLEAR. ROOF
 FRAMING PLAN ON SHEET S-1 SHOW THE STRUCTURAL ROOF
 FRAMING MEMBERS BEING SPACED MORE THAN 24" O.C. AND IT
 LOOKS LIKE THE CORNER IS NOT PROPERLY FRAMED TO SUPPORT
 THE REQUIRED LOADS, SPECIALLY AT THE CANTILEVERED ROOF
 AREA ON THE NORTH CORNER OF THE ROOF. PROVIDE COMPLETE
 FRAMING DETAIL/SPECIFICATIONS FOR BOTH CORNERS. SPECIFY
 ALL FRAMING MEMBERS AND CONNECTORS AT ALL ENDS. SEC.
 R301.1 FBC-RESIDENTIAL AND SEC. 107.2.1 CITY
 AMENDMENTS.
  
 B)BASED ON THE ROOF FRAMING PLAN ON SHEET S-1 AND THE
 TYPICAL WALL SECTION ON SHEET A-3, IT LOOKS LIKE THE
 INTENTION OF THE ARCHITECT IS TO DESIGN AN UNVENTED
 ATTIC. ARCHITECT TO PROVIDE COMPLETE SPECIFICATIONS
 SHOWING COMPLIANCE WITH SEC. R806.5 FBC-RESIDENTIAL FOR
 UNVENTED ATTIC AND UNVENTED ENCLOSED RAFTER ASSEMBLIES.
 TYPICALLY, THIS IS DONE USING FOAM INSULATION.
 NOTE: IF SPECIFYING FOAM INSULATION, THEN PROVIDE ICC
 EVALUATION REPORT REVIEWED BY THE ARCHITECT OF RECORD
 PRIOR TO SUBMITTAL.
 NOTE: COORDINATE WITH ITEM #7(D) BELOW.
  
 3- OK
 4- OK
  
 ORIGINAL COMMENT:
 5-PROVIDE COMPLETE WIND DESIGN CRITERIA. SEC. R301.2.1
 FBC-RESIDENTIAL.
 SPECIFY BUILDING EXPOSURE, ULTIMATE AND NOMINAL WIND
 SPEED.
  
 6- OK
  
 ORIGINAL COMMENT:
 7- TYPICAL WALL SECTION ON SHEET A-3:
 A)PROVIDE SPECIFICATIONS CLEARLY SHOWING HOW COMPLYING
 WITH THE NEW 2020 CODE REQUIREMENT FOR ROOFING
 UNDERLAYMENT. SEC. R905.1.1.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 PROVIDE PRODUCT APPROVAL OF PEEL AND STICK UNDERLAYMENT
 SPECIFIED BY THE ARCHITECT. NOTE: PEEL AND STICK
 UNDERLAYMENT SHALL BE APPROVED FOR SHINGLES OVER 30#
 ASPHALT FELT AS SPECIFIED BY THE ARCHITECT.
  
 B)OK
 C)OK
  
 D)WALL SECTION SPECIFIES R-30 CEILING INSULATION.
 CLEARLY SPECIFY WHAT TYPE OF INSULATIONS IS PROPOSED.
 BUTT INSULATION OR FOAM INSULATION. ALSO, IT IS NOT
 CLEAR IF R-30 INSULATION WILL FIT IN THIS CEILING AREA.
 VERIFY AS REQUIRED. WALL SECTION SHOWS ROOF RAFTERS BUT
 IT SPECIFIES ROOF TRUSSES. COORDINATE WITH ITEM #2
 ABOVE.
 NOTE: IF SPECIFYING FOAM INSULATION, THEN PROVIDE ICC
 EVALUATION REPORT REVIEWED BY THE ARCHITECT OF RECORD
 PRIOR TO SUBMITTAL.
  
 RESPONSE:
 BASED ON THE ROOF FRAMING PLAN ON SHEET S-1 AND THE
 TYPICAL WALL SECTION ON SHEET A-3, IT LOOKS LIKE THE
 INTENTION OF THE ARCHITECT IS TO DESIGN AN UNVENTED
 ATTIC. ARCHITECT TO PROVIDE COMPLETE SPECIFICATIONS
 SHOWING COMPLIANCE WITH SEC. R806.5 FBC-RESIDENTIAL FOR
 UNVENTED ATTIC AND UNVENTED ENCLOSED RAFTER ASSEMBLIES.
 TYPICALLY, THIS IS DONE USING FOAM INSULATION. REVISE
 AS REQUIRED AND REVISE INSULATION R-VALUE ACCORDINGLY.
  
 NOTE: IF SPECIFYING FOAM INSULATION, THEN PROVIDE ICC
 EVALUATION REPORT REVIEWED BY THE ARCHITECT OF RECORD
 PRIOR TO SUBMITTAL.
  
 E) OK
  
 F)WALL SECTION SPECIFIES SOFFIT VENTS AT 96" O.C.
 SOFFIT NEEDS CROSS VENTILATION AS REQUIRED BY SEC.
 R806.1 FBC-RESIDENTIAL. WALL SECTIONS SHOWS ROOF
 RAFTERS. ROOF RAFTERS DON'T PROVIDE CROSS VENTILATION
 WHEN THE VENTS ARE SPACED AT 96" O.C. THIS NEED TO BE
 COORDINATED WITH ITEM #2 ABOVE AND REVISE WALL SECTION
 SPECIFICATIONS AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 COORDINATE WITH ITEM #7(D) ABOVE.
  
 ORIGINAL COMMENT:
 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)ROOF SHINGLES.
  
 RESPONSE:
 NOA 20-0318.05 SUBMITTED IS ONLY FOR THE RIDGE CAP
 SHINGLES. NEED TO PROVIDE THE PRODUCT APPROVAL FOR TH
 SHINGLES ALSO.
  
 B)PEEL AND STICK UNDERLAYMENT SPECIFIED BY THE
 ARCHITECT. NOTE: PEEL AND STICK UNDERLAYMENT SHALL BE
 APPROVED FOR SHINGLES OVER 30# ASPHALT FELT AS
 SPECIFIED BY THE ARCHITECT.
  
 9- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 TO AVOID MORE DELAYS, PLEASE FEEL FREE TO CONTACT ME IF
 YOU HAVE ANY QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved