Plan Review Notes For Permit 21040876 |
Permit Number |
21040876 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-05-26 14:44:11 | ROOFING REVIEW COMMENTS | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | PERMIT #21040876 | | | | 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | 61G20-3.001 FOR | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO | | INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT | | APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF | | RECORD PRIOR TO SUBMITTAL): | | | | A)ROOF SHINGLES. | | | | 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | | | |
|