2021-05-26 14:35:57 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #21040876 |
| |
| 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 1106 |
| FBC-EXISTING BUILDING AND SEC. R101.5 FBC-ENERGY |
| CONSERVATION. |
| NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL |
| REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID |
| CONFLICTS/DELAYS. |
| |
| 2- PROVIDE COMPLETE ROOF FRAMING PLAN FOR THE ADDITION. |
| CLEARLY SPECIFY ALL FRAMING MEMBERS AND CONNECTORS. |
| ALSO, CLEARLY SPECIFY CONNECTION TO EXISTING. |
| SEC. R301.2.1 FBC-RESIDENTIAL. |
| NOTE: TYPICAL WALL SECTION ON SHEET A-3 SPECIFIES ROOF |
| TRUSSES. IT IS NOT CLEAR HOW TRUSSES ARE BUILT IF ONLY |
| TOP CHORD IS SHOWN. COORDINATE WITH ITEM #6 BELOW. |
| REVISE/CLARIFY. |
| |
| 3- PROVIDE COMPLETE BEAM AND HEADER SCHEDULE. PROVIDE |
| COMPLETE SPECIFICATIONS FOR RAKED BEAM SHOWN ON THE |
| WEST ELEVATION. PROVIDE SPECIFICATIONS FOR BEAM ABOVE |
| NEW OPENING WHERE EXISTING DOOR AND WINDOW WILL BE |
| REMOVED TO ALLOW FOR THE ADDITION. |
| SEC. R301.2.1 FBC-RESIDENTIAL. |
| |
| 4- PROVIDE COMPLETE FOUNDATION PLAN FOR THE ADDITION. |
| CLEARLY SPECIFY ALL FOOTINGS. ALSO, CLEARLY SPECIFY |
| CONNECTION TO EXISTING. |
| SEC. R301.2.1 FBC-RESIDENTIAL. |
| |
| 5- PROVIDE COMPLETE WIND DESIGN CRITERIA. SEC. R301.2.1 |
| FBC-RESIDENTIAL. |
| SPECIFY BUILDING EXPOSURE, ULTIMATE AND NOMINAL WIND |
| SPEED. |
| |
| 5- SHEET A-2: |
| A)EXISTING INTERIOR LIVING SPACE, ADDITION INTERIOR |
| LIVING SPACE AND ADDITION PORCH BUILDING AREAS SHOWN |
| UNDER THE SCOPE OF WORK DON'T MATCH BUILDING AREAS |
| SHOWN ON PLANS SUBMITTED. ALSO, THESE BUILDING AREAS |
| DON'T MATCH CITY RECORDS AND BUILDINGS AREAS SHOWN IN |
| PALM BEACH COUNTY PROPERTY APPRAISAL WEBSITE. |
| CLARIFY/REVISE AS REQUIRED. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| B) REVISE CODE REFERENCES. CURRENT ASCE 7 EDITION |
| REFERENCED IN THE CURRENT FBC 2020 IS THE ASCE 7-16 NOT |
| ASCE 7-10. REVISE AS REQUIRED. |
| CHAPTER 553 F.S. |
| |
| C) DOOR SCHEDULE SHOWN DOESN'T MATCH DOOR SHOWN ON |
| PLANS. REVISE/CLARIFY AS REQUIRED. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| 6- TYPICAL WALL SECTION ON SHEET A-3: |
| A)PROVIDE SPECIFICATIONS CLEARLY SHOWING HOW COMPLYING |
| WITH THE NEW 2020 CODE REQUIREMENT FOR ROOFING |
| UNDERLAYMENT. SEC. R905.1.1.1 FBC-RESIDENTIAL. |
| |
| B) THERE IS A NOTE TO SEE ELEVATIONS FOR ROOF PITCH. |
| ROOD PITCH IS NOT SPECIFIED IN THE ELEVATIONS. SPECIFY |
| ROOF PITCH. SEC. R905.2.2 FBC-RESIDENTIAL. |
| |
| C)PROVIDE SPECIFICATIONS FOR THE CONCRETE SLAB VAPOR |
| BARRIER AS REQUIRED BY SEC. R506.2.3 FBC-RESIDENTIAL. |
| CLEARLY SPECIFY THE REQUIRED THICKNESS. |
| |
| D)WALL SECTION SPECIFIES R-30 CEILING INSULATION. |
| CLEARLY SPECIFY WHAT TYPE OF INSULATIONS IS PROPOSED. |
| BUTT INSULATION OR FOAM INSULATION. ALSO, IT IS NOT |
| CLEAR IF R-30 INSULATION WILL FIT IN THIS CEILING AREA. |
| VERIFY AS REQUIRED. WALL SECTION SHOWS ROOF RAFTERS BUT |
| IT SPECIFIES ROOF TRUSSES. COORDINATE WITH ITEM #2 |
| ABOVE. |
| NOTE: IF SPECIFYING FOAM INSULATION, THEN PROVIDE ICC |
| EVALUATION REPORT REVIEWED BY THE ARCHITECT OF RECORD |
| PRIOR TO SUBMITTAL. |
| |
| E) REVISE CLARIFY WALL INSULATION. WALL SECTION |
| SPECIFIES R-7.5 WALL INSULATION, WHILE KEY NOTE #1 ON |
| SHEET A-2 SPECIFIED R-4.1 WALL INSULATION. REVISE AS |
| REQUIRED TO MATCH. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| F)WALL SECTION SPECIFIES SOFFIT VENTS AT 96" O.C. |
| SOFFIT NEEDS CROSS VENTILATION AS REQUIRED BY SEC. |
| R806.1 FBC-RESIDENTIAL. WALL SECTIONS SHOWS ROOF |
| RAFTERS. ROOF RAFTERS DON'T PROVIDE CROSS VENTILATION |
| WHEN THE VENTS ARE SPACED AT 96" O.C. THIS NEED TO BE |
| COORDINATED WITH ITEM #2 ABOVE AND REVISE WALL SECTION |
| SPECIFICATIONS AS REQUIRED. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| G) WALL SECTION DOESN'T SPECIFY CONNECTION OF NEW ROOF |
| FRAMING MEMBER TO EXISTING WALL. PROVIDE INFORMATION. |
| SEC. R301.2.1 FBC-RESIDENTIAL. |
| |
| 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| 61G20-3.001 FOR |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO |
| INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT |
| APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL): |
| |
| A)ROOF SHINGLES. |
| |
| B)SLIDING GLASS DOORS. |
| |
| C) SINGLE SWING DOOR. |
| |
| 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| NOTE: COORDINATE WITH DOOR AND WINDOW SCHEDULES SHOWN |
| ON PLANS TO AVOID CONFLICTS/DELAYS. |
| |
| 9- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW. |
| VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S |
| OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS |
| REQUIRED BY SEC. 109.3 CITY AMENDMENTS. UPDATE |
| VALUATION OR PROVIDE COPY OF SIGNED CONTRACTS INCLUDING |
| DESIGN PROFESSIONAL FEES. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |