2021-05-26 14:35:57RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21040876
  
 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 1106
 FBC-EXISTING BUILDING AND SEC. R101.5 FBC-ENERGY
 CONSERVATION.
 NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 2- PROVIDE COMPLETE ROOF FRAMING PLAN FOR THE ADDITION.
 CLEARLY SPECIFY ALL FRAMING MEMBERS AND CONNECTORS.
 ALSO, CLEARLY SPECIFY CONNECTION TO EXISTING.
 SEC. R301.2.1 FBC-RESIDENTIAL.
 NOTE: TYPICAL WALL SECTION ON SHEET A-3 SPECIFIES ROOF
 TRUSSES. IT IS NOT CLEAR HOW TRUSSES ARE BUILT IF ONLY
 TOP CHORD IS SHOWN. COORDINATE WITH ITEM #6 BELOW.
 REVISE/CLARIFY.
  
 3- PROVIDE COMPLETE BEAM AND HEADER SCHEDULE. PROVIDE
 COMPLETE SPECIFICATIONS FOR RAKED BEAM SHOWN ON THE
 WEST ELEVATION. PROVIDE SPECIFICATIONS FOR BEAM ABOVE
 NEW OPENING WHERE EXISTING DOOR AND WINDOW WILL BE
 REMOVED TO ALLOW FOR THE ADDITION.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 4- PROVIDE COMPLETE FOUNDATION PLAN FOR THE ADDITION.
 CLEARLY SPECIFY ALL FOOTINGS. ALSO, CLEARLY SPECIFY
 CONNECTION TO EXISTING.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 5- PROVIDE COMPLETE WIND DESIGN CRITERIA. SEC. R301.2.1
 FBC-RESIDENTIAL.
 SPECIFY BUILDING EXPOSURE, ULTIMATE AND NOMINAL WIND
 SPEED.
  
 5- SHEET A-2:
 A)EXISTING INTERIOR LIVING SPACE, ADDITION INTERIOR
 LIVING SPACE AND ADDITION PORCH BUILDING AREAS SHOWN
 UNDER THE SCOPE OF WORK DON'T MATCH BUILDING AREAS
 SHOWN ON PLANS SUBMITTED. ALSO, THESE BUILDING AREAS
 DON'T MATCH CITY RECORDS AND BUILDINGS AREAS SHOWN IN
 PALM BEACH COUNTY PROPERTY APPRAISAL WEBSITE.
 CLARIFY/REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 B) REVISE CODE REFERENCES. CURRENT ASCE 7 EDITION
 REFERENCED IN THE CURRENT FBC 2020 IS THE ASCE 7-16 NOT
 ASCE 7-10. REVISE AS REQUIRED.
 CHAPTER 553 F.S.
  
 C) DOOR SCHEDULE SHOWN DOESN'T MATCH DOOR SHOWN ON
 PLANS. REVISE/CLARIFY AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 6- TYPICAL WALL SECTION ON SHEET A-3:
 A)PROVIDE SPECIFICATIONS CLEARLY SHOWING HOW COMPLYING
 WITH THE NEW 2020 CODE REQUIREMENT FOR ROOFING
 UNDERLAYMENT. SEC. R905.1.1.1 FBC-RESIDENTIAL.
  
 B) THERE IS A NOTE TO SEE ELEVATIONS FOR ROOF PITCH.
 ROOD PITCH IS NOT SPECIFIED IN THE ELEVATIONS. SPECIFY
 ROOF PITCH. SEC. R905.2.2 FBC-RESIDENTIAL.
  
 C)PROVIDE SPECIFICATIONS FOR THE CONCRETE SLAB VAPOR
 BARRIER AS REQUIRED BY SEC. R506.2.3 FBC-RESIDENTIAL.
 CLEARLY SPECIFY THE REQUIRED THICKNESS.
  
 D)WALL SECTION SPECIFIES R-30 CEILING INSULATION.
 CLEARLY SPECIFY WHAT TYPE OF INSULATIONS IS PROPOSED.
 BUTT INSULATION OR FOAM INSULATION. ALSO, IT IS NOT
 CLEAR IF R-30 INSULATION WILL FIT IN THIS CEILING AREA.
 VERIFY AS REQUIRED. WALL SECTION SHOWS ROOF RAFTERS BUT
 IT SPECIFIES ROOF TRUSSES. COORDINATE WITH ITEM #2
 ABOVE.
 NOTE: IF SPECIFYING FOAM INSULATION, THEN PROVIDE ICC
 EVALUATION REPORT REVIEWED BY THE ARCHITECT OF RECORD
 PRIOR TO SUBMITTAL.
  
 E) REVISE CLARIFY WALL INSULATION. WALL SECTION
 SPECIFIES R-7.5 WALL INSULATION, WHILE KEY NOTE #1 ON
 SHEET A-2 SPECIFIED R-4.1 WALL INSULATION. REVISE AS
 REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 F)WALL SECTION SPECIFIES SOFFIT VENTS AT 96" O.C.
 SOFFIT NEEDS CROSS VENTILATION AS REQUIRED BY SEC.
 R806.1 FBC-RESIDENTIAL. WALL SECTIONS SHOWS ROOF
 RAFTERS. ROOF RAFTERS DON'T PROVIDE CROSS VENTILATION
 WHEN THE VENTS ARE SPACED AT 96" O.C. THIS NEED TO BE
 COORDINATED WITH ITEM #2 ABOVE AND REVISE WALL SECTION
 SPECIFICATIONS AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 G) WALL SECTION DOESN'T SPECIFY CONNECTION OF NEW ROOF
 FRAMING MEMBER TO EXISTING WALL. PROVIDE INFORMATION.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)ROOF SHINGLES.
  
 B)SLIDING GLASS DOORS.
  
 C) SINGLE SWING DOOR.
  
 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: COORDINATE WITH DOOR AND WINDOW SCHEDULES SHOWN
 ON PLANS TO AVOID CONFLICTS/DELAYS.
  
 9- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. UPDATE
 VALUATION OR PROVIDE COPY OF SIGNED CONTRACTS INCLUDING
 DESIGN PROFESSIONAL FEES.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,