2021-04-27 08:09:55 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 21040866 |
| 4/27/21 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE DEMOLITION AND ELECTRICAL PLANS INDICATE NEW |
| LOCATIONS FOR THE KITCHEN SINK AND WASHING MACHINE, AND |
| REPLACED FIXTURES ETC. PLEASE PROVIDE PLUMBING PLANS |
| INCLUDING A SCOPE OF WORK OUTLINE, SANITARY AND WATER |
| RISER DRAWINGS, AND NEW FIXTURE SPECIFICATIONS- |
| SECTIONS 107.2.1 & 107.3.5.3 WPB. |
| |
| 2) SHEET 2- SHOWER PAN: LINERS SHALL BE PITCHED |
| ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL |
| (2-PERCENT SLOPE) AND SHALL BE SLOPED TOWARD THE |
| FIXTURE DRAINS- SECTION 421.5.2 FBC P. |
| |
| 3) RELOCATING DRAIN OUTLETS WILL REQUIRE THE FLOOR TO |
| BE X-RAYED TO IN ORDER TO LOCATE REINFORCING STEEL OR |
| POST STRESSED FLOOR TENDONS. PLEASE PLACE A NOTE ON THE |
| PLANS TO VERIFY COMPLIANCE WILL BE MET- SECTION 107.2.1 |
| WPB. |
| |
| 4) NEW DRAIN PIPE PENETRATIONS OF THE EXISTING SLAB |
| WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACE |
| AROUND THE PIPING. PROVIDE A UL TESTED AND APPROVED |
| FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION 315.1 |
| FBC P AND SECTION 714.4.1.2 FBC B. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |