2021-05-13 10:50:31 | PLAN REVIEW BUILDING |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER PX3169 1&2 FAMILY - SFP306 |
| INSPECTOR BN4338 |
| BUILDING OFFICIAL BU1635 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| 2017 NEC |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| NOTICE: A PROVISO HAS BEEN PLACED ON THE SITE PLAN: |
| SITE WALLS SHALL BE BY SEPERATE PERMIT. CT |
| |
| |
| 1. VALUE |
| CITY OF WPB CHPT109.3 BUILDING PERMIT VALUATIONS. |
| |
| VALUE CANNOT BE DETERMINED AT THIS TIME. PROJECT DATA |
| STATES ACCESSORY ADDITION IS 159 SF. THIS APPEARS LOW |
| BUT I CANNOT VERIFY DUE TO MISSING DEMENSIONS ON PLANS. |
| UPDATE YOUR PLANS WITH ALL REQUIRED DEMENSIONS. |
| |
| FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE |
| BUILDING OFFICIAL |
| |
| 2. PROVIDE THE FLORIDA STATE PRODUCT APPROVAL COVER |
| SHEETS FOR ALL FLORIDA PRODUCT APPROVALS SUBMITTED. THE |
| COVER SHEET PROVIDES THE APPROVAL NUMBER, CODE VERSION, |
| AND STATUS, FBC R 301. |
| (COVER SHEETS ARE NOT REQUIRED FOR MIAMI DADE NOAS.) |
| |
| 3. PROVIDE A SITE DRAINAGE PLAN. |
| FBC R401.3 SITE DRAINAGE |
| PROVIDE A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH |
| FBC R401.3 DRAINAGE. |
| |
| 4. PROVIDE AN ENERGY SUBMITTAL. |
| FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| COMPLIANCE BY SECTION 405. |
| |
| 5. CANNOT VERIFY SF OF ADDITION. PROVIDE PLANS WITH |
| REQUIRED DEMENSIONS. |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| 6. SHOW COMPLIANCE WITH REQUIRED SMOKE ALARMS PER R314. |
| R314.1 GENERAL. |
| SMOKE ALARMS SHALL COMPLY WITH NFPA 72 AND SECTION |
| R314. |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| |
| |
| |