2021-04-26 20:40:19 | ECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. SEPARATE PERMIT REQUIRED FOR ACCESSORY STRUCTURE FBC |
| 105.1 |
| |
| 2. NOTES SAY AFCI PROTECTION IN BEDROOMS ONLY, THAT IS |
| NOT CODE COMPLIANT. AFCI PROTECTION MUST BE PER |
| NEC210.12A&B |
| NEW PANEL SCHEDULE DOES NOT SHOW AMPERAGE OF PANEL ( |
| SHOULD SAY 200AMP) |
| |
| 3. SMOKE DETECTOR TO BE TIED INTO LOCAL LIGHTING |
| CIRCUIT. CANNOT BE STAND ALONE.FBC-R APPENDIX J |
| |
| 4. NO LOAD CALC SHOWN FOR 100AMP PANEL IN ACCESSORY |
| BUILDING NEC220 |
| |
| 5. NO SMOKE ALARMS SHOWN IN EITHER STRUCTURE. FBC-R 314 |
| &315 |
| |
| 6. NEW PANEL SCHEDULE SHOWS 100AMP SUB PANEL BUT SUB |
| PANEL IN MAIN STRUCTURE NOT SHOWN. |
| |
| 100AMP PANEL IN ACCESSORY BUILDING SHOWN TO HAVE OWN |
| MAIN DISC OFF METER CAN?? PLEASE CLARIFY AND FIX PLANS |
| AND PANEL SCHEDULE ACCORDINGLY. |
| |
| 7. MUST HAVE RECEPTACLE IN FRONT AND REAR OF DWELLING |
| OUTSIDE. NEC 210.52E1 |
| |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| FRANK GIAQUINTO III |
| ELECTRICAL INSPECTOR |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| [email protected] |
| CELL: 561-657-1653 |
| |