Plan Review Notes For Permit 21040839 |
Permit Number |
21040839 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-06-23 15:11:31 | 1ST REVIEW FBC-2020 RES. GAS | | PERMIT- 21040839 | | 6/23/2021 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE GAS RISER DRAWING SHALL BEAR THE PRINTED NAME, | | LICENSE NUMBER AND SIGNATURE OF THE CONTRACTOR OR | | QUALIFIER WHO PREPARED THE DRAWING- SECTION 107.2.1 | | WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025. | | | | 2) THE SURVEY IS INCORRECTLY SPECIFYING THE GENERATOR | | TO BE LOCATED 5 FT. FROM DOOR AND WINDOW OPENINGS. | | MINIMUM 10 FT. CLEARANCE FOR THE GENERATOR EXHAUST TO | | THE OPENINGS IS REQUIRED- SECTION R303.5.1 FBC RES. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | | | |
|