Date |
Text |
2021-05-03 16:52:53 | CODES IN EFFECT |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 |
| 7TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW: |
| |
| 1) PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET |
| OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE |
| SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE |
| DESIGN. THIS PERSON MUST BE A LICENSED DESIGN |
| PROFESSIONAL |
| OR THE ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE |
| CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481 |
| |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 |
| 7TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| 1) PLEASE SHOW LOCATION OF ALL SMOKE DETECTORS (NEW AND |
| EXISTING) FBC 2020 |
| |
| 2) PROVIDE COMPLIANCE: "NOT LESS THAN 90 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LUMINAIRES SHALL HAVE |
| AN EFFICACY OF AT LEAST 45 LUMENS-PER-WATT OR SHALL |
| UTILIZE LAMPS WITH AN EFFICACY OF NOT LESS THAN 65 |
| LUMENS-PER-WATT?. |
| A NOTE WILL SUFFICE. FBC EC R404.1 |
| |
| 3) PLEASE PROVIDE A LIST OF ELECTRICAL SYMBOLS FOR THE |
| ELECTRICAL DRAWINGS (FOR EXAMPLE NOT CLEAR WHAT |
| RECEPTACLES LABELED CTOP ARE) FBC 107 |
| |
| 4) PERMIT APPLICATION WAS SUBMITTED AFTER JAN 2021 SO |
| THE NEC 2017 AND FBC 2020 CODES APPLY. PLEASE UPDATE |
| YOUR CODE REFERENCES TO REFLECT THE NEW CODES IN |
| EFFECT. FBC 107 |
| |
| 5) ARE ALL RECEPTACLES AND LIGHTS SHOWN NEW? |
| |
| |
| |
| ENRIQUE QUINONEZ PE |
| ELECTRICAL PLANS EXAMINER |
| DEVELOPMENT SERVICES |
| CITY OF WEST PAM BEACH |
| 401 CLEMATIS STREET, 1ST FLOOR |
| WEST PALM BEACH, FL 33401 |
| |
| FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS, |
| 561-805-6746. |
| |