Plan Review Notes
Plan Review Notes For Permit 21040833
Permit Number 21040833
Review Stop B
Sequence Number 1
Notes
Date Text
2021-04-27 17:14:04WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21040833
 ADD: 400 N, FLAGLER DR. SUITES: 1903 / 1904
 CONT: RICHARD MCDONALD CONSTRUCTION CO. INC.
 TEL: 561-795-4055
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. APRIL 27TH/ 2021
 ACTION: DENIED
  
 1) IT APPEARS THAT WORK IS BEING COMPLETED IN 2 UNITS
 1903 & 1094. THE PROPOSED TENANT SPACES TRANSGRESS
 LEGAL BOUNDARY LINES BETWEEN THE CONDOMINIUM UNITS
 WHICH WILL NEED TO BE COMBINED TO FORM 'THE SITE'. A
 'UNITY OF TITLE' SHALL BE RECORDED AT THE COUNTY
 COURTHOUSE. SUBMIT A COPY OF THE RECORDED 'UNITY OF
 TITLE' DOCUMENT SO THAT FBC TABLE 601 BOUNDARY LINE
 REQUIREMENTS MAY BE DEEMED NOT APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
  
 2) SHEET A1.1.1:
 2A) UNDER THE HEADING OF PROJECT DATA THE DESIGN WIND
 PRESSURES ARE GIVEN FOR WINDOWS AND DOORS AS WORST
 CASE. POSITIVE + 63.3 PSF (ASSUMED VASD) AND THE
 NEGATIVE PRESSURES ARE GIVEN AT -84.7 (ASSUMED VASD).
 THE ENGINEERING EXPRESS SHEET IS HIGHLIGHTED EXPOSURE
 D, INTERIOR WALL ZONE 4, MEAN ROOF HEIGHT AT 220 MEAN
 ROOF HEIGHT 0F 220. THE WORST-CASE PRESSURES FOR WALL
 ZONE 4 WOULD BE +67.0/ - 67.0 @ 10 SQ. FT. SHOP DRAWING
 STAMP OF APPROVAL BY YOUR OFFICE. WHY THE DIFFERENCE IN
 REQUIRED PRESSURES? 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED. THE SUBMITTED PRODUCT APPROVALS CANNOT BE
 REVIEWED UNTIL THE UNTIL THE DISCREPANCY IN PRESSURES
 IS RESOLVED.
  
 2B) TRASH CHUTE LABELED 004AND DOOR TO TRASH CHUTE IS
 LABELED 106. THE DOOR SCHEDULE HAS THE DOOR 106 AS
 GREAT ROOM AND NO FIRE RATING. PLEASE SEE IN THE 2020
 FBC-B SECTION 713.13.3 CHUTE ACCESS ROOMS. OPENING
 PROTECTIVES OF NOT LESS THAN ? HRS. AND SELF-CLOSING OR
 AUTOMATIC CLOSING UPON THE DETECTION OF SMOKE IN
 ACCORDANCE WITH 716.5.9.3.
  
 2C) PLEASE REVIEW DOORS IDENTIFIED AS 101 AND 110 ENTRY
 DOORS FROM THE ELEVATOR LOBBY. THE DOOR SCHEDULE DOES
 NOT SHOW THESES DOORS WITH A FIRE RATING. PLEASE REVIEW
 IN THE 2020 FBC-BUILDING CODE SECTION 3006.3 HOISTWAY
 PROTECTION AND WHICH METHOD OF PROTECTION IS GOING TO
 BE PROVIDED.
  
 3) SHEET A1.1.2 FLOOR FINISH SCHEDULE INDICATES THE
 FLOOR FINISH IS CURRENTLY TBD/ TO BE DETERMINED. UNTIL
 THE FLOOR FINISHES ARE KNOWN WE CAN NOT SPECULATE ON IF
 THE UNDERLAYMENT WAS TESTED WITH THAT FINISH MATERIAL
 FOR ANY OF THE REQUIRED 3 TESTS, IIC, STC AND FLAME
 SPREAD. PLEASE NOTE THE CITY IS IN RECEIPT OF THE
 PROFLEX PRODUCT RCU 500/ 6 INCH SLAB/ FOR USE WITH
 QUARRY TILE.
  
 FLOOR INSULATION (FBC-B 2020) FOR TILE, STONE, MARBLE,
 VINYL AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 3A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 3B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 3C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4) SHEET A1.1.2 THE WALL FINISH SCHEDULE E IS VERY
 VAGUE WHEN IT COMES TO THE BATHROOM & RESTROOM AREAS.
 2020 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS COMMENT
 IS A RESULT OF THE BUILDING OFFICIAL INTERPRETATION ON
 06/2020. IN BATHROOMS, RESTROOMS & SERVICE SINK AREAS
 EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH HARD,
 NON-ABSORBENT SURFACE.
  
 4A) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 4B) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS
 SHALL COMPLY WITH 1210.2.
  
 4C) 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS AND
 PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH
 SECTIONS 1210.1 THROUGH 1210.4.
  
 4D) 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS
 A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS
 AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER
 RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE
 FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND
 THE MANUFACTURE?S RECOMMENDATIONS.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  