2021-05-20 15:56:45 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | PAGE E-600 | | | | 1) TRANSFORMER ON FOURTH FLOOR HAS A GEC LABELED #7 | | WHAT IS IT GOING TO CONNECT TO? | | | | PAGE E-601 | | | | !) LOAD CALCULATIONS FOR BOTH THE FEEDER AND BRANCH | | CIRCUITS SHALL BE FIGURED AT 125% PER 625.41 OF THE NEC | | | | 2) PANEL CHS2 IS IT A MLO OR MCB? |
|