2021-05-20 15:56:45ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-600
  
 1) TRANSFORMER ON FOURTH FLOOR HAS A GEC LABELED #7
 WHAT IS IT GOING TO CONNECT TO?
  
 PAGE E-601
  
 !) LOAD CALCULATIONS FOR BOTH THE FEEDER AND BRANCH
 CIRCUITS SHALL BE FIGURED AT 125% PER 625.41 OF THE NEC
  
 2) PANEL CHS2 IS IT A MLO OR MCB?