Plan Review Notes
Plan Review Notes For Permit 21040699
Permit Number 21040699
Review Stop M
Sequence Number 2
Notes
Date Text
2021-07-16 15:35:12THE MECHANICAL EQUIPMENT SIZING CALCULATIONS MUST BE
 SIGNED AND SEALED BY EITHER A LICENSED ENGINEER, AND
 LICENSED ARCHITECT OR THE MECHANICAL CONTRACTOR THAT
 HAS THE PERMIT TO INSTALL THE SYSTEM FOR THIS LOCATION
 CAN PRINT THEIR NAME AND SIGN THE DRAWINGS. PLEASE
 ADDRESS ORIGINAL REVIEW COMMENTS LISTED BELOW.
  
 1ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21040699
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENERGY CALCULATIONS MUST INCLUDE THE GARAGE DOOR
 BEFORE THIS AREA COULD BE CONSIDERED TO BE CONDITIONED.
 FBC RES R101.4.2.4 AND R402.1
 2) I HAVE NOT REVIEWED THE MECHANICAL ON THIS PROJECT
 AT THIS TIME. I WILL REVIEW AFTER THE ENERGY
 CALCULATIONS ARE CORRECTED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  