Plan Review Notes For Permit 21040699 |
Permit Number |
21040699 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-07-16 15:35:12 | THE MECHANICAL EQUIPMENT SIZING CALCULATIONS MUST BE | | SIGNED AND SEALED BY EITHER A LICENSED ENGINEER, AND | | LICENSED ARCHITECT OR THE MECHANICAL CONTRACTOR THAT | | HAS THE PERMIT TO INSTALL THE SYSTEM FOR THIS LOCATION | | CAN PRINT THEIR NAME AND SIGN THE DRAWINGS. PLEASE | | ADDRESS ORIGINAL REVIEW COMMENTS LISTED BELOW. | | | | 1ST REVIEW FBC-2020 MECHANICAL | | PERMIT-21040699 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE ENERGY CALCULATIONS MUST INCLUDE THE GARAGE DOOR | | BEFORE THIS AREA COULD BE CONSIDERED TO BE CONDITIONED. | | FBC RES R101.4.2.4 AND R402.1 | | 2) I HAVE NOT REVIEWED THE MECHANICAL ON THIS PROJECT | | AT THIS TIME. I WILL REVIEW AFTER THE ENERGY | | CALCULATIONS ARE CORRECTED. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|