Date |
Text |
2021-07-23 18:37:43 | |
| RESIDENTIAL (R3)ADDITION, SECOND REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #21040699 |
| |
| 1- OK |
| |
| 2- SHEET S-2.01: |
| A) OK |
| |
| ORIGINAL COMMENT: |
| B) REVISE ALL THE DESIGN PRESSURES (DOORS/WINDOWS, |
| ROOF) TO REFLECT THE REVISED BUILDING EXPOSURE REQUIRED |
| BY ITEM #2(A) ABOVE. SEC. R301.2.1 FBC-RESIDENTIAL. |
| NOTE: CLARIFY IF THE SPECIFIED DESIGN PRESSURES ARE |
| ULTIMATE DESIGN PRESSURES OR NOMINAL. |
| |
| RESPONSE: |
| (1)ARCHITECT SPECIFIED THAT ROOF PRESSURES SHOWN ON THE |
| ROOF ZONE UPLIFT DIAGRAM ARE ULTIMATE DESIGN PRESSURES. |
| THIS PRESSURES ARE TOO LOW IF THEY ARE THE ULTIMATE |
| DESIGN PRESSURES. REVISE AS REQUIRED. |
| |
| (2)ARCHITECT SPECIFIED THAT DOORS AND WINDOWS DESIGN |
| PRESSURES SHOWN ON SHEET S-1.01 ARE ULTIMATE DESIGN |
| PRESSURES. THIS PRESSURES ARE TOO LOW IF THEY ARE THE |
| ULTIMATE DESIGN PRESSURES. REVISE AS REQUIRED. |
| ALSO, NEED TO SPECIFY THE DESIGN PRESSURES FOR THE NEW |
| FRENCH DOORS ON THE MAIN HOUSE. |
| |
| ORIGINAL COMMENT: |
| C)REVISE ROOF ZONE UPLIFT DIAGRAM TO REFLECT ALL ROOF |
| ZONES CHANGES DONE FOR 2020 FBC-RESIDENTIAL. SEE FIGURE |
| R301.2(7) FBC-RESIDENTIAL AND REVISE AS REQUIRED. |
| NOTE: CLARIFY IF THE SPECIFIED DESIGN PRESSURES ARE |
| ULTIMATE DESIGN PRESSURES OR NOMINAL. |
| |
| RESPONSE: |
| DIAGRAM SUBMITTED WAS NOT REVISED. SEE NEW ROOF ZONES |
| CHANGES DONE FOR 2020 FBC-RESIDENTIAL. SEE NEW FIGURE |
| R301.2(7) FBC-RESIDENTIAL AND NEW TABLE R301.2(2) |
| FBC-RESIDENTIAL AND REVISE AS REQUIRED. |
| NEED TO REVISE THE ROOF DESIGN PRESSURES ACCORDINGLY |
| SHOWING EACH NEW ROOF ZONE. ALSO, ULTIMATE DESIGN |
| PRESSURES SHOWN ARE TOO LOW FOR EXPOSURE "D". |
| REVISE AS REQUIRED. |
| |
| D) OK |
| |
| ORIGINAL COMMENT: |
| E)LIVE AND DEAD LOADS SPECIFIED UNDER THE DESIGN |
| CRITERIA AND STRUCTURAL NOTES ARE NOT CLEAR. CLEARLY |
| SPECIFY THE TOP CHORD LIVE LOADS, TOP CHORD DEAD LEADS |
| AND BOTTOM CHORD LIVE LOADS, DEAD LOADS. SEC. R301.1 |
| FBC-RESIDENTIAL AND TABLE R301.5 FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| TRUSS TOP AND BOTTOM DEAD LOADS ARE STILL NO SPECIFIED. |
| DESIGNER OF RECORD NEEDS TO SPECIFY ALL THE DESIGN |
| LOADS, INCLUDING THE DEAD LOADS. |
| |
| |
| 3- OK |
| |
| ORIGINAL COMMENT: |
| 4- BREEZEWAY UNDERLAYMENT IS NOT CLEAR. SPECIFICATIONS |
| ON SHEET A-3.01 AND SPECIFICATIONS ON ROOF FRAMING PLAN |
| DON'T MATCH. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 |
| CITY AMENDMENTS. |
| |
| RESPONSE: |
| NOW IS NOT CLEAR IF THE BREEZEWAY IS GOING TO HAVE |
| METAL ROOF OR CLAY TILE. NEW NOTE ON THE ROOF FRAMING |
| PLAN SPECIFIES CLAY BARREL TILE BUT EXTERIOR ELEVATIONS |
| AND BUILDING SECTIONS SHOW METAL ROOF. REVISE/CLARIFY |
| AS REQUIRED. |
| |
| ORIGINAL COMMENT: |
| 5- PROVIDE STRUCTURAL BUCK DETAIL AND SPECIFICATIONS |
| FOR GARAGE OVERHEAD DOOR, EXTERIOR SWING DOORS AND |
| WINDOWS. |
| SEC. R301.2.1 FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| (1)STRUCTURAL BUCK DETAILS ON SHEETS A5.01 AND A5.02 |
| SPECIFY STRUCTURAL BUCK SIZE BUT DON'T SPECIFY "TAPCON" |
| SIZE AND SPACING. THERE IS A NOTE STATING "REFER TO |
| STRUCTURAL DRAWINGS FOR SIZING, SPACING AND EMBEDMENT |
| SPECIFICATIONS" BUT THERE ARE NO SUCH SPECIFICATIONS ON |
| THE STRUCTURAL DRAWINGS. DESIGNER OF RECORD NEEDS TO |
| PROVIDE COMPLETE FASTENING SPECIFICATIONS. |
| |
| (2)STRUCTURAL BUCK DETAILS ON SHEETS A5.03 SPECIFY |
| STRUCTURAL BUCK SIZE BUT DON'T SPECIFY ANCHOR TYPE, |
| SIZE AND SPACING. THERE IS A NOTE STATING "PER MANUF. |
| SPECS. AND N.O.A". |
| DESIGNER OF RECORD NEEDS TO PROVIDE COMPLETE FASTENING |
| SPECIFICATIONS OF THE STRUCTURAL BUCK. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| NOTE: DETAILS ON SHEET A5-03 ARE TITLED "SWING" DOOR. |
| THIS IS INCORRECT. THIS GARAGE DOOR IS NOT AN SWING |
| DOOR. REVISE AS REQUIRED. |
| |
| 6- OK |
| |
| 7- ENERGY CALCULATIONS: |
| A)OK |
| B)OK |
| |
| ORIGINAL COMMENT: |
| C)THERE IS NO INFORMATION ON PAGE 3 OF 4 FOR THE |
| OVERHEAD GARAGE DOOR. PROVIDE COMPLETE INFORMATION. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| RESPONSE: |
| REPEAT COMMENT. STILL NO INFORMATION FOR THE OVERHEAD |
| GARAGE DOOR. ALSO, DOOR INFORMATION SHOWN ON PAGE 3 OF |
| 4 IS INCORRECT. THE 3'X9' DOOR IS IS NOT WOOD AND IS A |
| GLAZED DOOR. SEE EXTERIOR ELEVATIONS. THIS DOOR |
| INFORMATION SHALL BE INCLUDED IN THE GLASS AREA AS |
| REQUIRED BY SEC. R405.5.3.3 FBC-ENERGY CONSERVATION. |
| REVISE AS REQUIRED. |
| |
| ORIGINAL COMMENT: |
| D)REVISE WINDOW INFORMATION ON PAGE 3 OF 4: |
| (1)MISSING INFORMATION FOR FRENCH DOOR GLAZING ON THE |
| EAST SIDE. SEC. R405.5.3.3 FBC-ENERGY CONSERVATION. |
| |
| RESPONSE: |
| REPEAT COMMENT. COORDINATE WITH RESPONSE TO ITEM 7(C) |
| ABOVE. |
| |
| ORIGINAL COMMENT: |
| (2)WINDOW OVERHANG SEPARATION DOESN'T MATCH PLANS. SEE |
| EXTERIOR ELEVATIONS AND REVISE AS REQUIRED. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| NEW COMMENT: |
| E)ENERGY CALCULATIONS FORM SUBMITTED IS NOT SIGNED BY |
| THE OWNER OR LEGAL AGENT. THE ENERGY FORM R405-2020 IS |
| REQUIRED TO BE SIGNED AND DATED BY THE OWNER, ARCHITECT |
| OR OWNER'S LEGALLY DESIGNATED AGENT AT THE BOTTOM OF |
| FORM SUBMITTED AS REQUIRED BY SEC. R103.1.1.2 |
| FBC-ENERGY CONSERVATION, PRIOR TO RECEIVING THE PERMIT |
| TO BEGIN CONSTRUCTION. |
| |
| F)THE ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD |
| SUBMITTED NOW IS NOT SIGNED BY THE BUILDER. BUILDER TO |
| SIGN AND COMPLETE THE ENERGY PERFORMANCE LEVEL (EPL) |
| DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY CONSERVATION. |
| |
| |
| 8- OK |
| |
| 9-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| 61G20-3.001 FOR |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO |
| INSTALLATION TO AVOID CONFLICTS/DELAYS): |
| |
| A)ROOF TILE ADHESIVE SPECIFIED BY THE ARCHITECT OF |
| RECORD ON SHEET S-1.01. SEE ROOF TILE NOA SUBMITTED FOR |
| LISTED ADHESIVES. AND CLEARLY MARK PADDY SIZE. |
| |
| NEW COMMENTS BASED ON DOOR SCHEDULE SUBMITTED NOW: |
| C)OVERHEAD GARAGE DOOR SIZE SPECIFIED ON DOOR SCHEDULE. |
| (18' X 9'). AND, NEED DOOR THAT MEETS THE DESIGN |
| PRESSURES SHOWN ON REVISED SHEET S1.01. |
| |
| D)SWING GARAGE DOOR SIZE SPECIFIED ON DOOR SCHEDULE |
| (3'X 9'). AND, NEED DOOR THAT MEETS THE DESIGN |
| PRESSURES SHOWN ON REVISED SHEET S1.01. |
| |
| 10-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. NOTE: NEED |
| TO REVISE PRODUCT APPROVALS LETTER. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |