2021-11-15 13:59:05 | NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING AUDIT |
| COMMENTS. |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #21040654 |
| |
| ORIGINAL COMMENT: |
| 1- ACCORDING TO SEC. R301.2.1.4.3 FBC-RESIDENTIAL, THIS |
| BUILDING IS LOCATED IN EXPOSURE "D" NOT EXPOSURE "C". |
| ENGINEER OF RECORD NEEDS TO REVISE THE BUILDING |
| EXPOSURE AND ALL DESIGN PRESSURES ACCORDINGLY. |
| NOTE: PRODUCT APPROVALS WILL BE AUDITED ONCE DESIGN |
| PRESSURES ARE REVISED. |
| |
| RESPONSE: |
| A)ENGINEER OF RECORD DIDN'T REVISE THE DOOR AND WINDOWS |
| DESIGN PRESSURES. NEED TO REVISE AS REQUIRED. SEC. |
| R301.2.1.4.3 FBC-RESIDENTIAL. |
| |
| B)NEW COMMENTS BASED ON TRUSS PACKAGE SUBMITTED: |
| (1)TRUSSES WERE DESIGNED BASED ON 2017 FBC AND ASCE |
| 7-10. THE CURRENT CODE IS 2020 FBC AND ASCE-7-16. |
| COMPLETE TRUSS PACKAGE NEEDS TO BE REVISED. |
| CHAPTER 553 F.S. |
| |
| (2)REVISED TRUSS PACKAGE NEEDS TO BE REVIEWED/APPROVED |
| IN WRITING BY THE ENGINEER OF RECORD PRIOR TO SUBMITTAL |
| TO THIS OFFICE. SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| ORIGINAL COMMENT: |
| 2- BASED ON THE SOIL REPORT SUBMITTED THERE ARE HEAVY |
| ORGANICS/MUCK THROUGHOUT THE BUILDING PAD AREA. THE |
| SOIL REPORT RECOMMENDATION IS TO DEMUCK THE BUILDING |
| PAD AREA. A SEPARATE PERMIT IS REQUIRED TO DEMUCK THE |
| BUILDING PAD AREA. CONTRACTOR TO SUBMIT PERMIT |
| APPLICATION WITH COMPLETE ENGINEER'S DEMUCKING |
| SPECIFICATIONS UNDER A SEPARATE PERMIT. SEC. 105.1 CITY |
| AMENDMENTS. |
| NOTE: BUILDING PERMIT WILL BE ISSUED WHEN THE DEMUCKING |
| WORK IS COMPLETED AND APPROVED. |
| |
| RESPONSE: |
| DEMUCKING PERMIT UNDER REVIEW. PERMIT #21101015. |
| |
| 3- OK. |
| |
| ORIGINAL COMMENT: |
| 4- ROOFING UNDERLAYMENT FL14317-R11 SUBMITTED IS |
| PENDING FBC APPROVAL. NEED TO SUBMIT APPROVED PRODUCT |
| APPROVAL. FAC 61G20-3.001. |
| NOTE: ENGINEER OF RECORD TO REVIEW AND APPROVED BEFORE |
| SUBMITTAL. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| 5- OK. SLIDING GLASS DOOR SUBMITTED BY MISTAKE. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR AUDIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |