2021-09-08 10:30:51 | NEW SINGLE FAMILY RESIDENCE (R3) BUILDING AUDIT |
| COMMENTS. |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #21040654 |
| |
| 1- ACCORDING TO SEC. R301.2.1.4.3 FBC-RESIDENTIAL, THIS |
| BUILDING IS LOCATED IN EXPOSURE "D" NOT EXPOSURE "C". |
| ENGINEER OF RECORD NEEDS TO REVISE THE BUILDING |
| EXPOSURE AND ALL DESIGN PRESSURES ACCORDINGLY. |
| NOTE: PRODUCT APPROVALS WILL BE AUDITED ONCE DESIGN |
| PRESSURES ARE REVISED. |
| |
| 2- BASED ON THE SOIL REPORT SUBMITTED THERE ARE HEAVY |
| ORGANICS/MUCK THROUGHOUT THE BUILDING PAD AREA. THE |
| SOIL REPORT RECOMMENDATION IS TO DEMUCK THE BUILDING |
| PAD AREA. A SEPARATE PERMIT IS REQUIRED TO DEMUCK THE |
| BUILDING PAD AREA. CONTRACTOR TO SUBMIT PERMIT |
| APPLICATION WITH COMPLETE ENGINEER'S DEMUCKING |
| SPECIFICATIONS UNDER A SEPARATE PERMIT. SEC. 105.1 CITY |
| AMENDMENTS. |
| NOTE: BUILDING PERMIT WILL BE ISSUED WHEN THE DEMUCKING |
| WORK IS COMPLETED AND APPROVED. |
| |
| 3- SHEET 4-4: ROOF SHEATHING SPECIFICATIONS IS NOT |
| CLEAR. NOTE LOCATED BELOW THE COMPONENT AND CLADDING |
| PRESSURE ZONES CHART DOESN'T MATCH THE ROOF SHEATHING |
| SPECIFICATIONS SHOWN ON THE COMPONENT AND CLADDING |
| PRESSURE ZONES CHART. REVISE AS REQUIRED TO MATCH. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| 4- ROOFING UNDERLAYMENT FL14317-R11 SUBMITTED IS |
| PENDING FBC APPROVAL. NEED TO SUBMIT APPROVED PRODUCT |
| APPROVAL. FAC 61G20-3.001. |
| NOTE: ENGINEER OF RECORD TO REVIEW AND APPROVED BEFORE |
| SUBMITTAL. |
| |
| 5- CLARIFY WHY SUBMITTING PRODUCT APPROVAL FOR SLIDING |
| GLASS DOORS IF THERE ARE NOT SLIDING GLASS DOORS IN |
| THIS PROJECT? |
| SEC. 1072.1 CITY AMENDMENTS. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR AUDIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |