2021-06-11 14:40:08FAILED
  
 ARCADE IDENTITY SIGN
  
 1) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE
 THAT ALL CONDUIT, CROSSOVERS, WIRING, JUNCTION BOXES,
 ETC. NECESSARY FOR THE SIGN'S ELECTRICAL CONNECTION TO
 BE CONCEALED AND NOT VISIBLE TO THE PUBLIC. THE
 RESUBMITTED DRAWINGS REMOVED THE JUNCTION BOX FROM THE
 PLANS; HOWEVER, NO CLARIFICATION WAS PROVIDED HOW THE
 ELECTRICAL CONNECTIONS ARE CONCEALED. THE NOTE THAT THE
 GC IS PROVIDING THE PRIMARY SOURCE INSIDE THE EXISTING
 ARCHWAY IS NOT SUFFICIENT. YOU MUST VERIFY HOW THIS IS
 CONCEALED (FOR EXAMPLE IF THERE IS AN AREA ABOVE THE
 ARCADE CEILING WERE THE ELECTRICAL CONNECTIONS ARE
 LOCATED).
  
 PERMITTED: 44.3 SF
 PROPOSED: 11.4 SF
  