Plan Review Notes
Plan Review Notes For Permit 21040564
Permit Number 21040564
Review Stop G
Sequence Number 1
Notes
Date Text
2021-04-29 08:32:031ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21040564
 4/29/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE GAS PIPING AND EQUIPMENT DEMOLITION PLANS
 AND SUBMIT A GAS SUB-PERMIT APPLICATION- SECTIONS 105.1
 & 107.2.1 FBC FG.
  
 2) THE SCOPE OF WORK ON THE PLAN SHALL INDICATE
 COMPLIANCE WITH SECTION 404.15 FOR GAS PIPE CAPPING,
 AND SECTIONS 406.7.1.1 & 406.7.1.3 FOR GAS PIPING
 REMOVED FROM SERVICE REQUIREMENTS.
 406.7.1.1 REMOVAL FROM SERVICE.
 WHERE EXISTING GAS PIPING IS OPENED, THE SECTION THAT
 IS OPENED SHALL BE ISOLATED FROM THE GAS SUPPLY AND THE
 LINE PRESSURE VENTED IN ACCORDANCE WITH SECTION
 406.7.1.3. WHERE GAS PIPING MEETING THE CRITERIA OF
 TABLE 406.7.1.1 IS REMOVED FROM SERVICE, THE RESIDUAL
 FUEL GAS IN THE PIPING SHALL BE DISPLACED WITH AN INERT
 GAS.
  
 406.7.1.3 OUTDOOR DISCHARGE OF PURGED GASES.
 THE OPEN END OF A PIPING SYSTEM BEING PRESSURE VENTED
 OR PURGED SHALL DISCHARGE DIRECTLY TO AN OUTDOOR
 LOCATION. PURGING OPERATIONS SHALL COMPLY WITH ALL OF
 THE FOLLOWING REQUIREMENTS:
 1. 1. THE POINT OF DISCHARGE SHALL BE CONTROLLED WITH A
 SHUTOFF VALVE.
 2. 2. THE POINT OF DISCHARGE SHALL BE LOCATED NOT LESS
 THAN 10 FEET FROM SOURCES OF IGNITION, NOT LESS THAN 10
 FEET FROM BUILDING OPENINGS AND NOT LESS THAN 25 FEET
 FROM MECHANICAL AIR INTAKE OPENINGS.
 3. 3. DURING DISCHARGE, THE OPEN POINT OF DISCHARGE
 SHALL BE CONTINUOUSLY ATTENDED AND MONITORED WITH A
 COMBUSTIBLE GAS INDICATOR THAT COMPLIES WITH SECTION
 406.7.1.4.
 4. 4. PURGING OPERATIONS INTRODUCING FUEL GAS SHALL BE
 STOPPED WHEN 90 PERCENT FUEL GAS BY VOLUME IS DETECTED
 WITHIN THE PIPE.
 5. 5. PERSONS NOT INVOLVED IN THE PURGING OPERATIONS
 SHALL BE EVACUATED FROM ALL AREAS WITHIN 10 FEET (3048
 MM) OF THE POINT OF DISCHARGE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  
2021-04-23 13:09:45DO THEY NEED A GAS PERMIT TO DISCONNECT ALL THE OLD
 LIGHT POLES (GAS).