2021-04-29 08:32:03 | 1ST REVIEW FBC-2020 FUEL GAS |
| PERMIT- 21040564 |
| 4/29/2021 |
| |
| CODES IN EFFECT: |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROVIDE GAS PIPING AND EQUIPMENT DEMOLITION PLANS |
| AND SUBMIT A GAS SUB-PERMIT APPLICATION- SECTIONS 105.1 |
| & 107.2.1 FBC FG. |
| |
| 2) THE SCOPE OF WORK ON THE PLAN SHALL INDICATE |
| COMPLIANCE WITH SECTION 404.15 FOR GAS PIPE CAPPING, |
| AND SECTIONS 406.7.1.1 & 406.7.1.3 FOR GAS PIPING |
| REMOVED FROM SERVICE REQUIREMENTS. |
| 406.7.1.1 REMOVAL FROM SERVICE. |
| WHERE EXISTING GAS PIPING IS OPENED, THE SECTION THAT |
| IS OPENED SHALL BE ISOLATED FROM THE GAS SUPPLY AND THE |
| LINE PRESSURE VENTED IN ACCORDANCE WITH SECTION |
| 406.7.1.3. WHERE GAS PIPING MEETING THE CRITERIA OF |
| TABLE 406.7.1.1 IS REMOVED FROM SERVICE, THE RESIDUAL |
| FUEL GAS IN THE PIPING SHALL BE DISPLACED WITH AN INERT |
| GAS. |
| |
| 406.7.1.3 OUTDOOR DISCHARGE OF PURGED GASES. |
| THE OPEN END OF A PIPING SYSTEM BEING PRESSURE VENTED |
| OR PURGED SHALL DISCHARGE DIRECTLY TO AN OUTDOOR |
| LOCATION. PURGING OPERATIONS SHALL COMPLY WITH ALL OF |
| THE FOLLOWING REQUIREMENTS: |
| 1. 1. THE POINT OF DISCHARGE SHALL BE CONTROLLED WITH A |
| SHUTOFF VALVE. |
| 2. 2. THE POINT OF DISCHARGE SHALL BE LOCATED NOT LESS |
| THAN 10 FEET FROM SOURCES OF IGNITION, NOT LESS THAN 10 |
| FEET FROM BUILDING OPENINGS AND NOT LESS THAN 25 FEET |
| FROM MECHANICAL AIR INTAKE OPENINGS. |
| 3. 3. DURING DISCHARGE, THE OPEN POINT OF DISCHARGE |
| SHALL BE CONTINUOUSLY ATTENDED AND MONITORED WITH A |
| COMBUSTIBLE GAS INDICATOR THAT COMPLIES WITH SECTION |
| 406.7.1.4. |
| 4. 4. PURGING OPERATIONS INTRODUCING FUEL GAS SHALL BE |
| STOPPED WHEN 90 PERCENT FUEL GAS BY VOLUME IS DETECTED |
| WITHIN THE PIPE. |
| 5. 5. PERSONS NOT INVOLVED IN THE PURGING OPERATIONS |
| SHALL BE EVACUATED FROM ALL AREAS WITHIN 10 FEET (3048 |
| MM) OF THE POINT OF DISCHARGE. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| CCOLE@WPB |
| |
2021-04-23 13:09:45 | DO THEY NEED A GAS PERMIT TO DISCONNECT ALL THE OLD |
| LIGHT POLES (GAS). |