Plan Review Notes
Plan Review Notes For Permit 21040372
Permit Number 21040372
Review Stop P
Sequence Number 1
Notes
Date Text
2021-05-03 05:12:581) SHT. A2.0 REFERS TO THE 2017 FLORIDA BUILDING CODE.
 THE CODE IN EFFECT FOR THIS PROJECT IS THE 2020 FLORIDA
 BUILDING CODE. REVISE THE CODE INFORMATION. WPB AMEND.
 TO FBC SEC. 107.2.1.
 2) THE NOTES ON THE PLANS ARE VERY LIGHT AND DIFFICULT
 TO READ. WPB AMEND. TO FBC SEC. 107.2.1.
 3) SHT. P101 - FLOOR DRAIN DETAIL - SUBMIT THE
 MANUFACTURER'S SPECIFICATIONS FOR THE TRAP GUARD INSET.
 WPB AMEND. TO FBC SEC. 107.2.1.
 4) SHT. P102 - THE FLOOR DRAIN SHALL BE DIRECTLY
 CONNECTED TO THE DRAINAGE SYSTEM OF THE BUILDING OR
 PREMISES PER FBC-PLUMBING SEC.301.3.
 5) INDICATE ON THE PLAN THE TYPE OF INFLUENT THAT WILL
 BE DISCHARGING INTO THE FLOOR DRAIN. WILL IT BE
 STORMWATER? IF SO, IT SHALL DRAIN TO AN APPROVED POINT
 OF DISPOSAL WHERE IT WILL NOT CONSTITUTE A NUISANCE
 CONDITION. FBC-PLUMBING SEC. 1101.2.
 6) PVC CANNOT BE USED FOR THE PIPING MATERIAL FOR THE
 HOSE BIBB. FBC-PLUMBING TABL 605.4.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  