Plan Review Notes
Plan Review Notes For Permit 21040282
Permit Number 21040282
Review Stop E
Sequence Number 1
Notes
Date Text
2021-04-15 22:41:18ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. LOAD CALC IS INCORRECT. A 3PHASE LOAD OF 21KW WOULD
 BE AROUND 59AMPS. PROVIDE ACCURATE LOAD CALC PER NEC220
  
 2. AFCI REQUIRED FOR ALL 15-20 AMP CIRCUITS ACCORDING
 TO NEC210.12 NOT 20AMP CIRCUITS ONLY AS ELECTRICAL NOTE
 ON PLAN STATES.
  
 3. SMOKE/CARBON ALARMS MUST BE TIED INTO LOCAL LIGHTING
 CIRCUIT, NOT ON SEPARATE INDIVIDUAL CIRCUIT. FBC-R
 APPENDIX J
  
 4. TAMPER PROOF RECEPTACLES REQUIRED PER NEC 406.12
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  