2021-04-15 22:41:18 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. LOAD CALC IS INCORRECT. A 3PHASE LOAD OF 21KW WOULD |
| BE AROUND 59AMPS. PROVIDE ACCURATE LOAD CALC PER NEC220 |
| |
| 2. AFCI REQUIRED FOR ALL 15-20 AMP CIRCUITS ACCORDING |
| TO NEC210.12 NOT 20AMP CIRCUITS ONLY AS ELECTRICAL NOTE |
| ON PLAN STATES. |
| |
| 3. SMOKE/CARBON ALARMS MUST BE TIED INTO LOCAL LIGHTING |
| CIRCUIT, NOT ON SEPARATE INDIVIDUAL CIRCUIT. FBC-R |
| APPENDIX J |
| |
| 4. TAMPER PROOF RECEPTACLES REQUIRED PER NEC 406.12 |
| |
| |
| |
| END OF COMMENTS. |
| |