Date |
Text |
2021-06-13 14:24:12 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 21040186 |
| ADD: 3910 N. FLAGLER DR. # 402 |
| CONT: BIG BEAR DEVELOPERS / CBC1251971 |
| TEL: 561-275-5955 |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: SUN. JUNE 13TH /2021 |
| ACTION: DENIED |
| |
| NO TRANSMITTAL LETTER IN THE 2ND REVIEW, WHERE THE |
| ANSWERS CAN BE FOUND IN REGARDS TO THE CODE QUESTIONS |
| ASKED. A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 1A) 2ND REQUEST. THE LETTER SUBMITTED BY BIG BEAR |
| DEVELOPERS IS A GREAT CONCERN. WITHIN THE LETTER THERE |
| IS A STATEMENT, WE HAVE BEEN PERFORMING INSPECTIONS ON |
| THE MEP PHASES OF THIS PROJECT TO TRY AND CONFIRM THAT |
| WORK HAS BEEN COMPLETED TO OUR SATISFACTION. THIS WAS |
| BEING DONE WHILE BIG BEAR DEVELOPERS YOURSELVES DID |
| WORK WITHOUT THE BENEFIT OF A PERMIT. THE INDIVIDUALS |
| THAT DID THE INSPECTIONS FOR THE MEP TRADES DO THEY |
| HAVE A STATE LICENSE A BN INSPECTORS LICENSE FOR EACH |
| OF THESE TRADES. WE WILL BE LOOKING INTO THIS VIOLATION |
| THROUGH THE BUILDING CODE ADMINISTRATORS AND INSPECTORS |
| BOARD. FLORIDA STATUTE 468.607. |
| |
| 1B) 2ND REQUEST. THE LETTER SUBMITTED TO THE BUILDING |
| DEPARTMENT FOR BIG BEAR DEVELOPERS IS SIGNED LUKE |
| FISHER. LUKE FISHER IS NOT THE QUALIFIER FOR BIG BEAR |
| DEVELOPERS, WHAT POSITION OF AUTHORITY DO YOU HAVE AND |
| WHY HASN?T THE QUALIFIER SHEA HOMES SIGNED THE LETTER |
| OF SUCH GREAT IMPORTANCE? 107.2.1.2 ADDITIONAL |
| INFORMATION IS REQUIRED. |
| |
| 2) 2ND REQUEST. THE LETTER FROM THE SIGERSON?S |
| INDICATES THAT ANNE SEGERSON DID DRAWINGS AND SPECIFIED |
| WHAT WAS NEEDED., AND THAT SHE IS AN INTERIOR DESIGNER. |
| PLEASE NOTE THAT WHEN LOOKING THROUGH THE STATE DBPR |
| (DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION |
| UNDER THE LICENSE CATEGORY ARCHITECTS AND INTERIOR |
| DESIGNERS, FLORIDA STATUTE 481.213 LICENSING |
| REQUIREMENTS. |
| |
| 3) 2ND REQUEST. THE SUBMITTED DRAWINGS WERE NOT |
| DESIGNED BY ANY DESIGN PROFESSIONAL, ARCHITECT, |
| INTERIOR DESIGNER NOR ENGINEER. CERTIFICATION BY |
| CONTRACTOR. THE CONTRACTOR (QUALIFIER) THAT CREATED / |
| DREW THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES |
| AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME, |
| SIGN YOUR NAME AND LICENSE NUMBER FOR THE TRADE YOU ARE |
| LICENSED IN AND PLANS DRAWN. |
| |
| 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE |
| EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) |
| ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) |
| (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT |
| WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE |
| CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. |
| THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET |
| OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR |
| OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME |
| AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN |
| AND PLANS DRAWN. |
| |
| FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE |
| DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR |
| NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE |
| PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD |
| HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND |
| PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER |
| ONE SHEET. |
| |
| 4) 2ND REQUEST. THERE WAS NEVER NO FLOORING PERMIT |
| APPLIED FOR OR ISSUED FOR THE INSTALLATION OF FLOORING. |
| THE HARDSHIP LETTER INDICATES THAT NEW FLOOR TILE WAS |
| ORDERED, PLEASE REVIEW THE REQUIREMENTS FOR NEW |
| FLOORING REQUIREMENTS. FLOOR INSULATION (FBC-B 2020) |
| FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR |
| TYPE II BUILDINGS SHOWING COMPLIANCE WITH: |
| |
| 4A) 2ND REQUEST. FBC-B 2020 1207.3 STRUCTURE-BORNE |
| SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS |
| OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| |
| 4B) 2ND REQUEST. FBC-B 2020 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| 4C) 2ND REQUEST. FLAME SPREAD- FBC-B 2020 603.1. |
| EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED |
| FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE |
| SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT |
| MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 5-6) COMPLIED. |
| |
| 7) 2ND REQUEST. 2020 FBC-B SHOWERS & TUBS 1210.3. |
| SHOWER COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER |
| HEADS SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO |
| A HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET. |
| |
| 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| 19 |
| IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| 561-718-9724. |
| WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| RETIRED. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| DEVELOPMENT SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |
| |