Plan Review Notes
Plan Review Notes For Permit 21040186
Permit Number 21040186
Review Stop B
Sequence Number 1
Notes
Date Text
2021-04-29 09:47:49WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21040186
 ADD: 3910 N. FLAGLER DR. # 402
 CONT: BIG BEAR DEVELOPERS
 TEL: 561-275-5955
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. APRIL 29TH/2021
 ACTION: DENIED
  
 1A) THE LETTER SUBMITTED BY BIG BEAR DEVELOPERS IS A
 GREAT CONCERN. WITHIN THE LETTER THERE IS A STATEMENT,
 WE HAVE BEEN PERFORMING INSPECTIONS ON THE MEP PHASES
 OF THIS PROJECT TO TRY AND CONFIRM THAT WORK HAS BEEN
 COMPLETED TO OUR SATISFACTION. THIS WAS BEING DONE
 WHILE BIG BEAR DEVELOPERS YOURSELVES DID WORK WITHOUT
 THE BENEFIT OF A PERMIT. THE INDIVIDUALS THAT DID THE
 INSPECTIONS FOR THE MEP TRADES DO THEY HAVE A STATE
 LICENSE A BN INSPECTORS LICENSE FOR EACH OF THESE
 TRADES. WE WILL BE LOOKING INTO THIS VIOLATION THROUGH
 THE BUILDING CODE ADMINISTRATORS AND INSPECTORS BOARD.
 FLORIDA STATUTE 468.607.
  
 1B) THE LETTER SUBMITTED TO THE BUILDING DEPARTMENT FOR
 BIG BEAR DEVELOPERS IS SIGNED LUKE FISHER. LUKE FISHER
 IS NOT THE QUALIFIER FOR BIG BEAR DEVELOPERS, WHAT
 POSITION OF AUTHORITY DO YOU HAVE AND WHY HASN?T THE
 QUALIFIER SHEA HOMES SIGNED THE LETTER OF SUCH GREAT
 IMPORTANCE? 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2) THE LETTER FROM THE SIGERSON?S INDICATES THAT ANNE
 SEGERSON DID DRAWINGS AND SPECIFIED WHAT WAS NEEDED.,
 AND THAT SHE IS AN INTERIOR DESIGNER. PLEASE NOTE THAT
 WHEN LOOKING THROUGH THE STATE DBPR ( DEPARTMENT OF
 BUSINESS AND PROFESSIONAL REGULATION UNDER THE LICENSE
 CATEGORY ARCHITECTS AND INTERIOR DESIGNERS, FLORIDA
 STATUTE 481.213 LICENSING REQUIREMENTS.
  
 3) THE SUBMITTED DRAWINGS WERE NOT DESIGNED BY ANY
 DESIGN PROFESSIONAL, ARCHITECT, INTERIOR DESIGNER NOR
 ENGINEER. CERTIFICATION BY CONTRACTOR. THE CONTRACTOR
 (QUALIFIER) THAT CREATED / DREW THE SET OF PLANS WILL
 NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS.
 PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE
 NUMBER FOR THE TRADE YOU ARE LICENSED IN AND PLANS
 DRAWN.
  
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
  
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 4) THE HARDSHIP LETTER INDICATES THAT NEW FLOOR TILE
 WAS ORDERED, PLEASE REVIEW THE REQUIREMENTS FOR NEW
 FLOORING REQUIREMENTS. FLOOR INSULATION (FBC-B 2020)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 4A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 4B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 4C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 5) THE PLANS ARE SILENT AS TO THE TUB/ SHOWER WALLS AND
 FINISHES. 2020 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS
 COMMENT IS A RESULT OF THE BUILDING OFFICIAL
 INTERPRETATION ON 06/2020. IN BATHROOMS, RESTROOMS &
 SERVICE SINK AREAS EPOXY PAINT IS NO LONGER CONSIDERED
 A SMOOTH HARD, NON-ABSORBENT SURFACE.
  
 5A) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 5B) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS
 SHALL COMPLY WITH 1210.2.
  
 5C) 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS AND
 PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH
 SECTIONS 1210.1 THROUGH 1210.4.
  
  
 6) 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS A
 BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS
 AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER
 RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE
 FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN
 INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND
 THE MANUFACTURE?S RECOMMENDATIONS.
  
 7) 2020 FBC-B SHOWERS & TUBS 1210.3. SHOWER
 COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS
 SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A
 HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET.
  
 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  