2021-04-26 14:26:30 | 04/27/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. THERE IS A GAS WATER TANK TYPE SHOWN ON PLANS AND NO |
| VENTING SHOWN. PLEASE PROVIDE A DETAIL FOR THE TYPE OF |
| APPLIANCE THAT WILL BE USED AND ITS VENTING PER THE WPB |
| AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| 2. THE FROM R 405-202 FLORIDA ENERGY EFFICIENCY HAS AN |
| ELECTRICAL TANKLESS @ AN EF 0.92, AND THE PLANS SHOW A |
| TANK TYPE AND THE GAS PLANS IT GIVES THE BTU?S FOR A |
| TANKLESS, AND, PLEASE CLARIFY AND CORRECT PER THE WPB |
| AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| 3. ON SHEET FS101, THERE IS A DOUBLE DETECTOR CHECK |
| BACKFLOW. PLEASE NOTE ON PLANS THAT A SEPARATE PERMIT |
| AND REVIEW IS REQUIRED PER THE WPB AMENDMENTS TO THE |
| FBC SEC. 105.1. |
| |
| 4. ON SHEET P101; |
| A. THERE IS A TANK-TYPE GAS WITH A REFERENCE CODE FOR |
| 2017, AND SEE COMMENT TWO FOR CLARIFICATION PER THE WPB |
| AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| B. DETAIL C-7 SHOWS A SUPPER AND A ROOF DRAIN THAT DOES |
| NOT APPLY TO THIS STRUCTURE. PLEASE PROVIDE ONE WITH |
| THE DETAIL FOR THE ONE IN THE BALCONY AREA PER THE WPB |
| AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| C. DETAIL B-3 REFERS TO AN ANTI-SCALDING DEVICE THAT IS |
| NOT REQUIRED FOR RESIDENTIAL APPLICATIONS. THIS MAY BE |
| OMITTED FROM DRAWING FOR FIELD CLARITY PER THE WPB |
| AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| D. ON DETAIL A-2, BEFORE THE METER, YOU HAVE AN NRV. |
| WHAT IS THIS DEVICE, AND WHAT IS THE PURPOSE. PLEASE |
| REMOVE OR CLARIFY PER THE WPB AMENDMENTS TO THE FBC |
| SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 5. ON SHEET P201; |
| A. HAVE THE BATHROOM GROUP DOWNSTAIRS IN ROOM ONE |
| ISOLATED FROM THE MAIN TRUCK LINE, AND THE WASHING |
| CONNECTED TO THE POWDER ROOM ON TWO SEPARATE SYSTEMS |
| PER THE 2020 FBC R3108.1 HORIZONTAL WET VENT PERMITTED. |
| |
| B. PLEASE PROVIDE A SECOND SANITARY RISER DIAGRAM FOR |
| THE LEFT UNIT PER THE WPB AMENDMENTS TO THE FBC SEC. |
| 107.3.5.3 (12) RESIDENTIAL PLUMBING. |
| |
| 6. THE WASHING MACHINE SHUT OFF VALVES SHALL BE |
| ACCESSIBLE WITHOUT MOVING OF THE UNITS AND WITHIN REACH |
| PER THE 2020 FBC SEC. R 2903.9.3. |
| |
| 7. THE PIPES UNDER SLAB NEED TO BE INSULATED WITH A |
| MINIMUM R-3 PER THE 2017 FBC SEC. RE 403.5.3. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| |