2021-04-26 14:26:3004/27/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THERE IS A GAS WATER TANK TYPE SHOWN ON PLANS AND NO
 VENTING SHOWN. PLEASE PROVIDE A DETAIL FOR THE TYPE OF
 APPLIANCE THAT WILL BE USED AND ITS VENTING PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 2. THE FROM R 405-202 FLORIDA ENERGY EFFICIENCY HAS AN
 ELECTRICAL TANKLESS @ AN EF 0.92, AND THE PLANS SHOW A
 TANK TYPE AND THE GAS PLANS IT GIVES THE BTU?S FOR A
 TANKLESS, AND, PLEASE CLARIFY AND CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 3. ON SHEET FS101, THERE IS A DOUBLE DETECTOR CHECK
 BACKFLOW. PLEASE NOTE ON PLANS THAT A SEPARATE PERMIT
 AND REVIEW IS REQUIRED PER THE WPB AMENDMENTS TO THE
 FBC SEC. 105.1.
  
 4. ON SHEET P101;
 A. THERE IS A TANK-TYPE GAS WITH A REFERENCE CODE FOR
 2017, AND SEE COMMENT TWO FOR CLARIFICATION PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. DETAIL C-7 SHOWS A SUPPER AND A ROOF DRAIN THAT DOES
 NOT APPLY TO THIS STRUCTURE. PLEASE PROVIDE ONE WITH
 THE DETAIL FOR THE ONE IN THE BALCONY AREA PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 C. DETAIL B-3 REFERS TO AN ANTI-SCALDING DEVICE THAT IS
 NOT REQUIRED FOR RESIDENTIAL APPLICATIONS. THIS MAY BE
 OMITTED FROM DRAWING FOR FIELD CLARITY PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 D. ON DETAIL A-2, BEFORE THE METER, YOU HAVE AN NRV.
 WHAT IS THIS DEVICE, AND WHAT IS THE PURPOSE. PLEASE
 REMOVE OR CLARIFY PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. ON SHEET P201;
 A. HAVE THE BATHROOM GROUP DOWNSTAIRS IN ROOM ONE
 ISOLATED FROM THE MAIN TRUCK LINE, AND THE WASHING
 CONNECTED TO THE POWDER ROOM ON TWO SEPARATE SYSTEMS
 PER THE 2020 FBC R3108.1 HORIZONTAL WET VENT PERMITTED.
  
 B. PLEASE PROVIDE A SECOND SANITARY RISER DIAGRAM FOR
 THE LEFT UNIT PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.3.5.3 (12) RESIDENTIAL PLUMBING.
  
 6. THE WASHING MACHINE SHUT OFF VALVES SHALL BE
 ACCESSIBLE WITHOUT MOVING OF THE UNITS AND WITHIN REACH
 PER THE 2020 FBC SEC. R 2903.9.3.
  
 7. THE PIPES UNDER SLAB NEED TO BE INSULATED WITH A
 MINIMUM R-3 PER THE 2017 FBC SEC. RE 403.5.3.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  
  