2021-04-23 14:23:071ST REVIEW FBC-2020 MECHANICAL
 PERMIT- 21040185
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ADDRESS ON THE PERMIT AND ADDRESS ON THE ENERGY
 CALCULATIONS DO NOT MATCH. PLEASE PROVIDE THE CORRECT
 ADDRESS ON BOTH DOCUMENTS. FBC 107.2.1
  
 2) PLEASE PROVIDE THE ADDRESS FOR THE PROJECT ON THE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS. THERE IS NO
 ADDRESS ON THE ONE SUBMITTED. FBC 107.2.1
  
 3) PLEASE PROVIDE A MASTER PLAN OF THE COMMUNITY
 SHOWING THE TOTAL NUMBER OF R-1 DUPLEX UNITS FOR THIS
 COMMUNITY. FBC 107.2.1
  
 4) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR THESE
 R-1 OCCUPANCIES BASED ON FBC 403.3.1.1 AND TABLE
 403.3.1.1 FOR TRANSIENT LODGING.
  
 5) PLEASE SHOW HOW THE OUTDOOR AIR WILL BE INTRODUCED
 INTO EACH UNIT ON THE DRAWINGS. FBC 107.2.1
  
 6) PLEASE PROVIDE A MINIMUM OF 100CFM MAKE UP AIR FOR
 THE DRYER CLOSET. FBC M 504.6
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728