Plan Review Notes
Plan Review Notes For Permit 21040185
Permit Number 21040185
Review Stop E
Sequence Number 1
Notes
Date Text
2021-04-23 10:05:12CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW:
  
 1) SHEET E101 GENERAL NOTE #24: NEW ENERGY CODE (2020
 7TH EDITION) REQUIRES THAT:
  
 "R 404.1 NOT LESS THAN 90 PERCENT OF THE LAMPS IN
 PERMANENTLY INSTALLED LUMINAIRES SHALL HAVE AN EFFICACY
 OF AT LEAST 45 LUMENS-PER-WATT OR SHALL UTILIZE LAMPS
 WITH AN EFFICACY OF NOT LESS THAN 65 LUMENS-PER-WATT."
  
 PLEASE UPDATE NOTE 24 TO REFLECT NEW ENERGY CODE
 REQUIREMENTS
  
 2) SMOKE DETECTORS/CARBON MONOXIDE ALARMS REQUIRED AS
 PER FBC R314, R315. PLEASE SHOW LOCATION ON DRAWINGS.
  
 3) PLEASE PROVIDE AVAILABLE SHORT CIRCUIT CURRENT AT
 ELECTRICAL PANELS FBC 107
  
 4) PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PAM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6746.
  