2021-04-20 10:54:36PLAN DENIED
 1) PROVIDE DUCT SIZE, GRILL SIZE, CFM ON GRILLS, SHOW
 BATHROOM EXHAUST ON A/C PLAN
 PROVIDE RANGE HOOD ON PLAN (CFM) AND PROVIDE EQUIPMENT
 SCHEDULE ON A/C PLAN.