2021-05-12 13:21:54 | 1ST REVIEW FBC-2020 MECHANICAL |
| PERMIT-21040041 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M-1: SF-1 MUST MEET FBC M 508.1.1 |
| 508.1.1 MAKEUP AIR TEMPERATURE. THE TEMPERATURE |
| DIFFERENTIAL BETWEEN MAKEUP AIR AND THE AIR IN THE |
| CONDITIONED SPACE SHALL NOT EXCEED 10?F (6?C) EXCEPT |
| WHERE THE ADDED HEATING AND COOLING LOADS OF THE MAKEUP |
| AIR DO NOT EXCEED THE CAPACITY OF THE HVAC SYSTEM. |
| |
| 2) SHEET M-6: PLEASE SHOW ON THE DRAWINGS THAT THE |
| SUPPLY AIR FOR THE MAKE UP AIR IS A MINIMUM OF 10 FT. |
| FROM ANY EXHAUST OR PLUMBING VENTS. FBC M 401.4 |
| |
| 3) SHEET M-7: IT APPEARS THAT THE DESIGNER IS CALLING |
| OUT BOTH 1 INCH THICK 22 GA. GALVANIZED STEEL MINERAL |
| WOOL PANEL TO PROTECT COMBUSTIBLES FROM DUCT AND UL |
| APPROVED FIRE BARRIER WRAP. ARE BOTH REQUIRED FOR THIS |
| DESIGN? IF NOT PLEASE REMOVE THE DESIGN NOT USED. FBC |
| 107.2.1 |
| |
| 4) PLEASE PROVIDE VENTING SPECIFICATIONS FOR THE FBM |
| BAKING MACHINE AND THE SINGLE RACK OVEN. FBC 107.2.1 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |