2021-05-17 07:23:13 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| FLORIDA BUILDING CODE 2020 7TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED |
| NFPA 70 2017 EDITION |
| |
| JAKE LEAHY BN, BU, PX |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6713 |
| [email protected] |
| |
| KITCHEN PENINSULAR NEXT TO RANGE NEEDS AN OUTLET TO |
| SERVE COUNTER TOP. SPACE NEXT TO RANGE IS MORE THAN 12" |
| AN OUTLET IS REQUIRED THERE ALSO. |
| |
| 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT LEAST ONE |
| RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH PENINSULAR |
| COUNTERTOP LONG DIMENSION SPACE WITH A LONG DIMENSION |
| OF 600 MM (24 IN.) OR GREATER AND A SHORT DIMENSION OF |
| 300 MM (12 IN.) OR GREATER. A PENINSULAR COUNTERTOP IS |
| MEASURED FROM THE CONNECTED PERPENDICULAR WALL. |
| (4) SEPARATE SPACES. COUNTERTOP SPACES SEPARATED BY |
| RANGETOPS, REFRIGERATORS, OR SINKS SHALL BE CONSIDERED |
| AS SEPARATE COUNTERTOP SPACES IN APPLYING THE |
| REQUIREMENTS OF 210.52(C)(1). IF A RANGE, |
| COUNTER-MOUNTED COOKING UNIT, OR SINK IS INSTALLED IN |
| AN ISLAND OR PENINSULAR COUNTERTOP AND THE DEPTH OF THE |
| COUNTERTOP BEHIND THE RANGE, COUNTER-MOUNTED COOKING |
| UNIT, OR SINK IS LESS THAN 300 MM (12 IN.), THE RANGE, |
| COUNTER-MOUNTED COOKING UNIT, OR SINK SHALL BE |
| CONSIDERED TO DIVIDE THE COUNTERTOP SPACE INTO TWO |
| SEPARATE COUNTERTOP SPACES. EACH SEPARATE COUNTERTOP |
| SPACE SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS IN |
| 210.52(C). |