Plan Review Notes
Plan Review Notes For Permit 21031651
Permit Number 21031651
Review Stop M
Sequence Number 3
Notes
Date Text
2021-08-20 14:20:453RD REVIEW FBC-2020 MECHANICAL
 PERMIT-21031651
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 9 OF ( THE MECHANICAL DRAWING CLEARLY
 INDICATES A NEW 5-TON UNIT AND THE REPLACEMENT OF THE
 4-TON UNIT. PROVIDE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC EC C403.2.1
  
 2) THIS APPEARS TO BE A CHANGE OF USE FROM BUSINESS TO
 A-2. THE CHANGE OF USE FROM AN OFFICE TO A
 RESTAURANT/LOUNGE WOULD REQUIRE A MECHANICAL LOAD
 CALCULATION AND WOULD REQUIRE AN OUTDOOR AIR
 CALCULATION FOR THIS NEW USE OF SPACE. I DO NOT SEE A
 MUA FOR THE HOOD ( NOT REQUIRED ON THIS PERMIT BUT AN
 OBSERVATION) SO ARE THE AHU?S MAKING UP FOR THE HOOD?
 FBC 107.2.1 AND FBC M 508
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  