Plan Review Notes
Plan Review Notes For Permit 21031651
Permit Number 21031651
Review Stop P
Sequence Number 2
Notes
Date Text
2021-07-20 16:06:44CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 2ND REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 PROVISO: PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1,
 PROVIDE AS A DEFERRED SUBMITTAL MANUFACTURER?S
 SPECIFICATION AND INSTALLATION GUIDE FOR THE
 MANUFACTURER'S SPEC/INSTALLATION MANUALS FOR WATER
 HEATERS. DOCUMENTS SHALL BE SUBMITTED, APPROVED AND ON
 SITE PRIOR TO FINAL INSPECTION. PROCEED AT YOUR OWN
 RISK.
  
 1.SECOND REQUEST: THE CENTERLINE OF THE WATER CLOSET
 SHALL BE 16 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM
 THE SIDE WALL OR PARTITION PER FBC ACC 604.2
  
 2.SECOND REQUEST: PER FBC 606.5 EXPOSED PIPES AND
 SURFACES. EXPOSED WATER SUPPLY & DRAINPIPES UNDER
 LAVATORIES AND SINKS SHALL BE INSULATED OR OTHERWISE
 CONFIGURED TO PROTECT AGAINST CONTACT.
  
 3.SECOND REQUEST: MIRRORS LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE40 INCHES (1015 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND
  
 4. THERE IS A KITCHEN WHICH INCLUDES A RANGE WITH A
 GREASE HOOD, AN APPARENT KITCHEN SINK WITH DISHWASHER.
 APPARENTLY, THERE WILL BE FOOD PREP. PER WPB FBC
 107.2.1, PROVIDE A GREASE INTERCEPTOR TO COMPLY WITH
 THE REQUIREMENTS OF FBC PL 1003.3.1. PER WPB FBC
 107.2.1, PROVIDE A SPECIFICATION, SCHEDULE, DETAIL AND
 CALCULATIONS FOR THE SAME. PLEASE NOTE, PER FBC PL
 1003.3.2, A FOOD WASTE DISPOSER SHALL NOT DISCHARGE TO
 A GREASE INTERCEPTOR.
 -GREASE INTERCEPTOR IS PROVIDED
 -SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE
 CALCULATIONS FOR GREASE INTERCEPTOR.
 -NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE DETAIL FOR
 UNDER GROUND GREASE INTERCEPTOR; CONCRETE PIT W/FOOT
 TRAFFIC LID FOR ACCESS? PROVIDE REBAR REINFORCEMENT
 DETAILS.
  
 5. SECOND REQUEST; PER WPB FBC 107.2.1, SUBMIT FOR
 REVIEW MANUFACTURER'S SPEC/INSTALLATION MANUAL FOR
 DISHWASHER. APPROVED MANUFACTURER'S SPEC/INSTALLATION
 MANUALS SHALL BE ON SITE PRIOR TO INSPECTION. PROVIDE
 SCHEDULE FOR THE SAME; ITEM SHALL COMPLY WITH FBC PL
 409.1; INDICATE APPROPRIATE STANDARDS FOR MACHINE.
 PROVIDE DETAIL FOR PLUMBING CONNECTIONS; COMPLY WITH
 REQUIREMENTS OF FBC PL 409.2, 409.3 AND 409.4 AS IS
 APPLICABLE.
 -RESPONSE INDICATES SUBMITTAL FOR DISHWASHER WAS
 INCLUDED FOR REVIEW. I CANNOT FIND.
  
 6. THE PLUMBING PLAN INDICATES THAT THE APPARENT
 KITCHEN SINK IN THE KITCHEN IS A SERVICE SINK. THE
 INTENT OF THE REQUIRED SERVICE SINK AS REQUIRED IN FBC
 PL TABLE 403.1, IS TO PROVIDE A SUITABLE FIXTURE FOR
 CUSTODIAL DUTIES/SERVICES. PER WPB FBC 107.2.1. PROVIDE
 A DESIGNATED SERVICE SINK THAT WILL MEET THE CRITERIA.
 PROVIDE A DETAIL FOR THE SAME. COMPLIED
 -NEW COMMENT: THE THREE-COMPARTMENT SINK DISCHARGING TO
 THE GREASE INTERCEPTOR THROUGH A FLOOR SINK NEEDS TO BE
 DESIGNATED A POT SINK; WPB FBC 107.2.1. THE FLOOR SINK
 SHALL BE VENTED WITH AN INDIVIDUAL VENT CONNECTING TO
 EXISTING VENT SYSTEM; FBC PL 909.1, 904.1. PROVIDE
 INDIRECT WASTE TO FLOOR SINK W/AIR GAP; FBC PL 802.1.7.
 -THE DISHWASHER SHALL ALSO DISCHARGE TO THE FLOOR SINK.
 PROVIDE INDIRECT WASTE TO FLOOR SINK W/AIR GAP; FBC PL
 802.1.7.
 -PER WPB FBC 107.2.1, PROVIDE A DETAIL SHOWING
 DISCHARGE OF BOTH TO FLOOR SINK.
 -NEW COMMENT: HAND SINK AND NEW MOP SINK SHALL NOT
 DISCHARGE TO THE GREASE INTERCEPTOR; FBC PL 1003.2.
 -NEW COMMENT: THE MOP SINK SHALL NOT BE WET VENTED BY
 THE HAND SINK; FBC PL 912.1. PROVIDE INDIVIDUAL VENT
 FOR MOP SINK; FBC 909.1 OR PROVIDE COMMON VENT; FBC PL
 911. SEE RED LINED DRAWING 10-P PLUMBING RISERS.
  
 7. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE FINISH
 WALL SCHEDULES FOR TOILET ROOMS AND SERVICE SINK.
 COMPLY WITH FBC PL 310.3 AND FBC 1210.2.2. WALLS AND
 PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE SINKS,
 URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4
 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE. PLEASE NOTE THAT FBC 1210.2.2 STIPULATES THAT
 THE MATERIAL BE "HARD." THE INTENT OF THIS SECTION IS
 THAT THE SURROUNDING MATERIAL SHOULD NOT BE OF A TYPE
 THAT IS EASILY DAMAGED SUCH THAT THE MATERIAL COULD
 BECOME ABSORBENT AND THUS, NOT READILY CLEANABLE AND
 SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH
 HIGHLY DURABLE PAINTS, DOES NOT MEET THE INTENT OF
 SECTION 1210.2.2. THE TYPICAL MATERIALS USED FOR THIS
 APPLICATION ARE CERAMIC TILE, FIBERGLASS REINFORCED
 PLASTIC (FRP) PANELS, PHENOLIC PANELS, LAMINATED
 PLASTIC PANELS, PAINTED STEEL AND STAINLESS STEEL.
 -RESPONSE: FINISHES ON THE PLAN. I CAN NOT FIND. PER
 WPB FBC 107.2.1, PLEASE INDICATE WHICH PLAN SHEET AND
 CLOUD THE NOTE(S)/SCHEDULE. PLEASE NOTE, THE ADDED MOP
 SINK SHALL ALSO COMPLY WITH FBC PL 310.3 AND FBC
 1210.2.2.
  
 8. COMPLIED
  
 9. COMPLIED
  
 10.SECOND REQUEST; PER WPB FBC 107.2.1, PROVIDE
 EQUIPMENT SCHEDULE FOR ACCUMIX TANKLESS WATER HEATER
 INDICATING MANUFACTURER, MODEL NUMBER, GPM AND
 ELECTRICAL CHARACTERISTICS; PROVIDE DETAIL. IF IT IS
 ALSO A WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS
 TO ASSE 1070, PROVIDE NOTE.
 -NEW COMMENT: DELETE MULTIPLE FIXTURES WATER TEMPERING
 DEVICE DETAIL; WPB FBC 107.2.1
  
 11. SEE PROVISO REGARDING DEFERRED SUBMITTALS: PER WPB
 FBC 107.2.1, PROVIDE EQUIPMENT SCHEDULE FOR TANK TYPE
 WATER HEATER INDICATING MANUFACTURER, MODEL NUMBER,
 STORAGE CAPACITY AND ELECTRICAL CHARACTERISTICS. ALL
 DRAWINGS/SCHEDULE OF TANK TYPE WATER HEATER STORAGE
 CAPACITY SHALL BE CONSISTENT WITH EACH OTHER.
  
 12. COMPLIED
  
 13.REGARDING NEW WATER HEATER DETAIL
 -PER WPB FBC 107.2.1, SPECIFY AND SIZE THE EXPANSION
 TANK.
 -RELIEF LINE SHALL DISCHARGE FULL SIZE TO PAN THROUGH
 AIR GAP OR TO THE EXTERIOR; FBC PL 504.6
 -REMOVE ALL REFERENCES TO RECIRCULATING PUMP
 -PROVIDE PAN W/3/4 INCH DRAIN TO EXTERIOR; 504.7
  
 14. COMPLIED
  
 15. ORIGINAL REQUEST: PER WPB FBC 107.2.1, PROVIDE
 PLUMBING/EQUIPMENT/ FIXTURE SCHEDULE TO INCLUDE NEW AND
 REMAINING EXISTING FIXTURES, EQUIPMENT INCLUDING
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 AS REQUIRED BY FBC PL 419.5,
 607.1.2 AND WATER-HAMMER ARRESTORS THAT CONFORM TO ASSE
 1010 AS REQUIRED FOR QUICK-CLOSING VALVES INCLUDING
 DISHWASHERS BY FBC PL 604.9. ADDITIONALLY, SHOW
 LOCATIONS ON RISER DIAGRAM AND IDENTIFY THE SAME.
 -NEW COMMENT: ICE MAKER IS NOTED IN RESPONSE BUT IS NOT
 INDICATED ON THE PLANS. PER WPB FBC 107.2.1, PROVIDE
 PLUMBING/EQUIPMENT/ FIXTURE SCHEDULE TO INCLUDE NEW AND
 REMAINING EXISTING FIXTURES.
 -PER WPB FBC 107.2.1, IDENTIFY ICE MAKER ON THE PLANS;
 PROVIDE DRAIN AND WATER. PROVIDE BACKFLOW PROTECTION IN
 THE COLD WATER SUPPLY PER FBC PL 608.1 AND INDIRECT
 WASTE TO A TRAPPED AND VENTED WASTE RECEPTACLE (HUB
 DRAIN IS ACCEPTABLE) PER FBC PL 802 (WASTE RECEPTACLE
 SHALL BE READILY ACCESSIBLE). ICE MACHINE SHALL NOT
 DISCHARGE TO THE GREASE INTERCEPTOR; FBC PL 1003.2.
 -WATER HAMMER ARRESTORS FOR DISHWASHER AND ICE MACHINE
 ARE NOT NOTED
  
 16.PER WPB FBC 107.2.1, PROVIDE SIZE OF EXISTING
 INCOMING WATER SERVICE AND SHOW LOCATION, TYPE AND SIZE
 OF EXISTING BACKFLOW PREVENTOR FOR WATER SERVICE.
 -NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE A DETAIL AND
 SPEC FOR NEW BFP. NEW BFP REQUIRES A SEPARATE PERMIT.
  
 17.SECOND REQUEST: PER WPB FBC 107.2.1, REVISE NOTE 11
 BY REPLACING THE DESIGNATED M COPPER WITH L AS PER
 COPPER & COPPER ALLOY TUBE AND PIPE STANDARDS PUBLISHED
 BY THE COPPER DEVELOPMENT ASSOCIATION STATES "SEAMLESS
 COPPER WATER TUBE IS MANUFACTURED IN SIZES 1/4 INCH
 THROUGH 12 INCH NOMINAL. TYPES K AND L ARE MANUFACTURED
 IN DRAWN TEMPER (HARD) 1/4 INCH THROUGH 12 INCH AND
 ANNEALED TEMPER (SOFT) COILS 1/4 INCH THROUGH 2 INCH
 WHILE TYPE M IS ONLY MANUFACTURED IN DRAWN (HARD)
 TEMPER 1/4 INCH THROUGH 12 INCH."
  
 18. COMPLIED
  
 19. COMPLIED
  
 20. COMPLIED
  
 21. COMPLIED
  
 22. COMPLIED.
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21031651 1254 OKEECHOBEE RD
  
  