Date |
Text |
2021-07-20 16:06:44 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1 |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 2ND REVIEW |
| |
| PLUMBING COMMENTS: DENIED |
| |
| PROVISO: PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, |
| PROVIDE AS A DEFERRED SUBMITTAL MANUFACTURER?S |
| SPECIFICATION AND INSTALLATION GUIDE FOR THE |
| MANUFACTURER'S SPEC/INSTALLATION MANUALS FOR WATER |
| HEATERS. DOCUMENTS SHALL BE SUBMITTED, APPROVED AND ON |
| SITE PRIOR TO FINAL INSPECTION. PROCEED AT YOUR OWN |
| RISK. |
| |
| 1.SECOND REQUEST: THE CENTERLINE OF THE WATER CLOSET |
| SHALL BE 16 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM |
| THE SIDE WALL OR PARTITION PER FBC ACC 604.2 |
| |
| 2.SECOND REQUEST: PER FBC 606.5 EXPOSED PIPES AND |
| SURFACES. EXPOSED WATER SUPPLY & DRAINPIPES UNDER |
| LAVATORIES AND SINKS SHALL BE INSULATED OR OTHERWISE |
| CONFIGURED TO PROTECT AGAINST CONTACT. |
| |
| 3.SECOND REQUEST: MIRRORS LOCATED ABOVE LAVATORIES OR |
| COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF |
| THE REFLECTING SURFACE40 INCHES (1015 MM) MAXIMUM ABOVE |
| THE FINISH FLOOR OR GROUND |
| |
| 4. THERE IS A KITCHEN WHICH INCLUDES A RANGE WITH A |
| GREASE HOOD, AN APPARENT KITCHEN SINK WITH DISHWASHER. |
| APPARENTLY, THERE WILL BE FOOD PREP. PER WPB FBC |
| 107.2.1, PROVIDE A GREASE INTERCEPTOR TO COMPLY WITH |
| THE REQUIREMENTS OF FBC PL 1003.3.1. PER WPB FBC |
| 107.2.1, PROVIDE A SPECIFICATION, SCHEDULE, DETAIL AND |
| CALCULATIONS FOR THE SAME. PLEASE NOTE, PER FBC PL |
| 1003.3.2, A FOOD WASTE DISPOSER SHALL NOT DISCHARGE TO |
| A GREASE INTERCEPTOR. |
| -GREASE INTERCEPTOR IS PROVIDED |
| -SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE |
| CALCULATIONS FOR GREASE INTERCEPTOR. |
| -NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE DETAIL FOR |
| UNDER GROUND GREASE INTERCEPTOR; CONCRETE PIT W/FOOT |
| TRAFFIC LID FOR ACCESS? PROVIDE REBAR REINFORCEMENT |
| DETAILS. |
| |
| 5. SECOND REQUEST; PER WPB FBC 107.2.1, SUBMIT FOR |
| REVIEW MANUFACTURER'S SPEC/INSTALLATION MANUAL FOR |
| DISHWASHER. APPROVED MANUFACTURER'S SPEC/INSTALLATION |
| MANUALS SHALL BE ON SITE PRIOR TO INSPECTION. PROVIDE |
| SCHEDULE FOR THE SAME; ITEM SHALL COMPLY WITH FBC PL |
| 409.1; INDICATE APPROPRIATE STANDARDS FOR MACHINE. |
| PROVIDE DETAIL FOR PLUMBING CONNECTIONS; COMPLY WITH |
| REQUIREMENTS OF FBC PL 409.2, 409.3 AND 409.4 AS IS |
| APPLICABLE. |
| -RESPONSE INDICATES SUBMITTAL FOR DISHWASHER WAS |
| INCLUDED FOR REVIEW. I CANNOT FIND. |
| |
| 6. THE PLUMBING PLAN INDICATES THAT THE APPARENT |
| KITCHEN SINK IN THE KITCHEN IS A SERVICE SINK. THE |
| INTENT OF THE REQUIRED SERVICE SINK AS REQUIRED IN FBC |
| PL TABLE 403.1, IS TO PROVIDE A SUITABLE FIXTURE FOR |
| CUSTODIAL DUTIES/SERVICES. PER WPB FBC 107.2.1. PROVIDE |
| A DESIGNATED SERVICE SINK THAT WILL MEET THE CRITERIA. |
| PROVIDE A DETAIL FOR THE SAME. COMPLIED |
| -NEW COMMENT: THE THREE-COMPARTMENT SINK DISCHARGING TO |
| THE GREASE INTERCEPTOR THROUGH A FLOOR SINK NEEDS TO BE |
| DESIGNATED A POT SINK; WPB FBC 107.2.1. THE FLOOR SINK |
| SHALL BE VENTED WITH AN INDIVIDUAL VENT CONNECTING TO |
| EXISTING VENT SYSTEM; FBC PL 909.1, 904.1. PROVIDE |
| INDIRECT WASTE TO FLOOR SINK W/AIR GAP; FBC PL 802.1.7. |
| -THE DISHWASHER SHALL ALSO DISCHARGE TO THE FLOOR SINK. |
| PROVIDE INDIRECT WASTE TO FLOOR SINK W/AIR GAP; FBC PL |
| 802.1.7. |
| -PER WPB FBC 107.2.1, PROVIDE A DETAIL SHOWING |
| DISCHARGE OF BOTH TO FLOOR SINK. |
| -NEW COMMENT: HAND SINK AND NEW MOP SINK SHALL NOT |
| DISCHARGE TO THE GREASE INTERCEPTOR; FBC PL 1003.2. |
| -NEW COMMENT: THE MOP SINK SHALL NOT BE WET VENTED BY |
| THE HAND SINK; FBC PL 912.1. PROVIDE INDIVIDUAL VENT |
| FOR MOP SINK; FBC 909.1 OR PROVIDE COMMON VENT; FBC PL |
| 911. SEE RED LINED DRAWING 10-P PLUMBING RISERS. |
| |
| 7. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE FINISH |
| WALL SCHEDULES FOR TOILET ROOMS AND SERVICE SINK. |
| COMPLY WITH FBC PL 310.3 AND FBC 1210.2.2. WALLS AND |
| PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE SINKS, |
| URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, |
| NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4 |
| FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR |
| STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS |
| SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY |
| MOISTURE. PLEASE NOTE THAT FBC 1210.2.2 STIPULATES THAT |
| THE MATERIAL BE "HARD." THE INTENT OF THIS SECTION IS |
| THAT THE SURROUNDING MATERIAL SHOULD NOT BE OF A TYPE |
| THAT IS EASILY DAMAGED SUCH THAT THE MATERIAL COULD |
| BECOME ABSORBENT AND THUS, NOT READILY CLEANABLE AND |
| SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH |
| HIGHLY DURABLE PAINTS, DOES NOT MEET THE INTENT OF |
| SECTION 1210.2.2. THE TYPICAL MATERIALS USED FOR THIS |
| APPLICATION ARE CERAMIC TILE, FIBERGLASS REINFORCED |
| PLASTIC (FRP) PANELS, PHENOLIC PANELS, LAMINATED |
| PLASTIC PANELS, PAINTED STEEL AND STAINLESS STEEL. |
| -RESPONSE: FINISHES ON THE PLAN. I CAN NOT FIND. PER |
| WPB FBC 107.2.1, PLEASE INDICATE WHICH PLAN SHEET AND |
| CLOUD THE NOTE(S)/SCHEDULE. PLEASE NOTE, THE ADDED MOP |
| SINK SHALL ALSO COMPLY WITH FBC PL 310.3 AND FBC |
| 1210.2.2. |
| |
| 8. COMPLIED |
| |
| 9. COMPLIED |
| |
| 10.SECOND REQUEST; PER WPB FBC 107.2.1, PROVIDE |
| EQUIPMENT SCHEDULE FOR ACCUMIX TANKLESS WATER HEATER |
| INDICATING MANUFACTURER, MODEL NUMBER, GPM AND |
| ELECTRICAL CHARACTERISTICS; PROVIDE DETAIL. IF IT IS |
| ALSO A WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS |
| TO ASSE 1070, PROVIDE NOTE. |
| -NEW COMMENT: DELETE MULTIPLE FIXTURES WATER TEMPERING |
| DEVICE DETAIL; WPB FBC 107.2.1 |
| |
| 11. SEE PROVISO REGARDING DEFERRED SUBMITTALS: PER WPB |
| FBC 107.2.1, PROVIDE EQUIPMENT SCHEDULE FOR TANK TYPE |
| WATER HEATER INDICATING MANUFACTURER, MODEL NUMBER, |
| STORAGE CAPACITY AND ELECTRICAL CHARACTERISTICS. ALL |
| DRAWINGS/SCHEDULE OF TANK TYPE WATER HEATER STORAGE |
| CAPACITY SHALL BE CONSISTENT WITH EACH OTHER. |
| |
| 12. COMPLIED |
| |
| 13.REGARDING NEW WATER HEATER DETAIL |
| -PER WPB FBC 107.2.1, SPECIFY AND SIZE THE EXPANSION |
| TANK. |
| -RELIEF LINE SHALL DISCHARGE FULL SIZE TO PAN THROUGH |
| AIR GAP OR TO THE EXTERIOR; FBC PL 504.6 |
| -REMOVE ALL REFERENCES TO RECIRCULATING PUMP |
| -PROVIDE PAN W/3/4 INCH DRAIN TO EXTERIOR; 504.7 |
| |
| 14. COMPLIED |
| |
| 15. ORIGINAL REQUEST: PER WPB FBC 107.2.1, PROVIDE |
| PLUMBING/EQUIPMENT/ FIXTURE SCHEDULE TO INCLUDE NEW AND |
| REMAINING EXISTING FIXTURES, EQUIPMENT INCLUDING |
| APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| CONFORMS TO ASSE 1070 AS REQUIRED BY FBC PL 419.5, |
| 607.1.2 AND WATER-HAMMER ARRESTORS THAT CONFORM TO ASSE |
| 1010 AS REQUIRED FOR QUICK-CLOSING VALVES INCLUDING |
| DISHWASHERS BY FBC PL 604.9. ADDITIONALLY, SHOW |
| LOCATIONS ON RISER DIAGRAM AND IDENTIFY THE SAME. |
| -NEW COMMENT: ICE MAKER IS NOTED IN RESPONSE BUT IS NOT |
| INDICATED ON THE PLANS. PER WPB FBC 107.2.1, PROVIDE |
| PLUMBING/EQUIPMENT/ FIXTURE SCHEDULE TO INCLUDE NEW AND |
| REMAINING EXISTING FIXTURES. |
| -PER WPB FBC 107.2.1, IDENTIFY ICE MAKER ON THE PLANS; |
| PROVIDE DRAIN AND WATER. PROVIDE BACKFLOW PROTECTION IN |
| THE COLD WATER SUPPLY PER FBC PL 608.1 AND INDIRECT |
| WASTE TO A TRAPPED AND VENTED WASTE RECEPTACLE (HUB |
| DRAIN IS ACCEPTABLE) PER FBC PL 802 (WASTE RECEPTACLE |
| SHALL BE READILY ACCESSIBLE). ICE MACHINE SHALL NOT |
| DISCHARGE TO THE GREASE INTERCEPTOR; FBC PL 1003.2. |
| -WATER HAMMER ARRESTORS FOR DISHWASHER AND ICE MACHINE |
| ARE NOT NOTED |
| |
| 16.PER WPB FBC 107.2.1, PROVIDE SIZE OF EXISTING |
| INCOMING WATER SERVICE AND SHOW LOCATION, TYPE AND SIZE |
| OF EXISTING BACKFLOW PREVENTOR FOR WATER SERVICE. |
| -NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE A DETAIL AND |
| SPEC FOR NEW BFP. NEW BFP REQUIRES A SEPARATE PERMIT. |
| |
| 17.SECOND REQUEST: PER WPB FBC 107.2.1, REVISE NOTE 11 |
| BY REPLACING THE DESIGNATED M COPPER WITH L AS PER |
| COPPER & COPPER ALLOY TUBE AND PIPE STANDARDS PUBLISHED |
| BY THE COPPER DEVELOPMENT ASSOCIATION STATES "SEAMLESS |
| COPPER WATER TUBE IS MANUFACTURED IN SIZES 1/4 INCH |
| THROUGH 12 INCH NOMINAL. TYPES K AND L ARE MANUFACTURED |
| IN DRAWN TEMPER (HARD) 1/4 INCH THROUGH 12 INCH AND |
| ANNEALED TEMPER (SOFT) COILS 1/4 INCH THROUGH 2 INCH |
| WHILE TYPE M IS ONLY MANUFACTURED IN DRAWN (HARD) |
| TEMPER 1/4 INCH THROUGH 12 INCH." |
| |
| 18. COMPLIED |
| |
| 19. COMPLIED |
| |
| 20. COMPLIED |
| |
| 21. COMPLIED |
| |
| 22. COMPLIED. |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| MOBILE 561-246-0882 |
| PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| THURSDAYS |
| |
| 21031651 1254 OKEECHOBEE RD |
| |
| |