2021-05-04 13:23:07 | 1ST REVIEW FBC-2020 MECHANICAL |
| PERMIT-21031651 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE INCLUDE A NOTE ON THE DRAWINGS THAT THE |
| KITCHEN HOOD AND REFRIGERATION WILL REQUIRE SEPARATE |
| PERMITS AND PLAN REVIEWS. FBC 107.2.1 |
| |
| 3) ACCORDING TO GIS THERE ARE 2 STRUCTURES ON THIS |
| PARCEL, PLEASE PROVIDE ADDRESS AND IDENTIFICATION AS TO |
| WHICH BUILDING IS PERMITTED ON THIS PROJECT. FBC |
| 107.2.1 |
| |
| 4) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| CALCULATIONS FOR THIS CHANGE OF USE. FBC M 312 AND FBC |
| EC C403.2.1 |
| |
| 5) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS BASED ON |
| EACH USE OF SPACE I.E. KITCHEN, SINCE THIS IS A SOCIAL |
| CLUB WITH ALCOHOL PLEASE FIGURE THE LARGE SITTING AREA |
| AS A BAR, STORAGE. FBC M 403.3.1.1 AND TABLE 403.3.1.1 |
| |
| 6) MECHANICAL SHEET: PLEASE LABEL EACH AHU CLEARLY, THE |
| ONE ON THE LEFT APPEARS TO BE NAMED BOTH AHU-1 AND |
| AHU-2. FBC 107.2.1 |
| |
| 7) PLEASE REMOVE THE RETURN IN THE KITCHEN AREAS AS YOU |
| CANNOT TAKE RETURN AIR FROM A KITCHEN. FBC M 601.5 (7) |
| |
| 8) PLEASE SHOW OUTDOOR AIR DUCT FOR AHU-2 RETURN. FBC |
| 107.2.1 |
| |
| 9) PLEASE SHOW CONDENSATE LINE FOR AHU-2 AND |
| TERMINATION LOCATION. FBC M 307 |
| |
| 10) PLEASE EXPLAIN, IS THE ?WINE CELLAR? A PIECE OF |
| REFRIGERATION EQUIPMENT? IF SO PLEASE PROVIDE THE |
| SPECIFICATIONS FOR THIS PIECE OF EQUIPMENT. FBC 107.2.1 |
| |
| 11) PROVIDE EQUIPMENT SIZING CALCULATIONS FOR WINE AHU. |
| FBC M 312 AND FBC EC C403.2.1 |
| |
| 12) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR THE |
| WINE ROOM. FBC M 403.3.1.1 AND TABLE 403.3.1.1 |
| |
| 13) PLEASE SHOW THE BATH EXHAUST FAN AND THE CFM?S. FBC |
| M TABLE 403.3.1.1 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |