Plan Review Notes
Plan Review Notes For Permit 21031651
Permit Number 21031651
Review Stop B
Sequence Number 1
Notes
Date Text
2021-05-12 16:30:58CHANGE OF OCCUPANCY
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWING 1 OF 9 FLOOR PLAN SHOWS "PROPOSED OCCUPANCY"
 AS "B" - PLEASE REMOVE OR CORRECT TO A-2.
 2) PLEASE SHOW CEILING HEIGHTS AND BOTTOM OF FALSE BEAM
 HEIGHTS - FBC 1208.2
 3) PLEASE PROVIDE A WINDOW SCHEDULE SHOWING THE SIZES
 OF THE EXTERIOR WINDOWS TO BE REPLACED.
 4) PLEASE SHOW THE TOILET PAPER DISPENSER LOCATION (7-9
 INCHES TO THE CENTER OF THE DISPENSER) FROM THE FACE OF
 THE TOILET TO COMPLY WITH FBC A604.7
 5) ACCESSIBLE REST ROOM DOOR CANNOT SWING INTO THE
 FIXTURE CLEAR FLOOR SPACE - SEE EXCEPTION AND SHOW THE
 REQUIRED FLOOR SPACE FBC A603.2.3
 6) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS AND
 DOORS. ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND
 MARKED APPROVED BY THE DESIGNER OF RECORD. FBC 107.3.4