2021-04-19 21:14:56 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT-21031623 |
| 4/19/2021 |
| |
| CODES IN EFFECT: |
| |
| FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH |
| EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH |
| EDITION 2020 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1- PLEASE INDICATE ON THE PLANS IN ALL AREAS THE MOST |
| CURRENT CODE CYCLE. THE CURRENT CODE CYCLE IS FBC 2020 |
| 2- ON PLAN PAGE P3 WATER HEATER NOTE: THERMAL EXPANSION |
| IS REQUIRED PER FBC 2020 SEC.607.3THERMAL EXPANSION |
| CONTROL. |
| WHERE A STORAGE WATER HEATER IS SUPPLIED WITH COLD |
| WATER THAT PASSES THROUGH A CHECK VALVE, PRESSURE |
| REDUCING VALVE OR BACKFLOW PREVENTER, A THERMAL |
| EXPANSION CONTROL DEVICE SHALL BE CONNECTED TO THE |
| WATER HEATER COLD WATER SUPPLY PIPE AT A POINT THAT IS |
| DOWNSTREAM OF ALL CHECK VALVES, PRESSURE REDUCING |
| VALVES AND BACKFLOW PREVENTERS. THERMAL EXPANSION |
| CONTROL DEVICES SHALL BE SIZED IN ACCORDANCE WITH THE |
| MANUFACTURER?S INSTRUCTIONS AND SHALL BE SIZED SUCH |
| THAT THE PRESSURE IN THE WATER DISTRIBUTION SYSTEM |
| SHALL NOT EXCEED THAT REQUIRED BY SECTION 604.8. |
| 3- IT APPEARS AS THOUGH THE HEAT RECIRCULATION PUMP |
| WILL BE INSTALLED OUTDOORS? PLEASE INDICATE HOW THE |
| RECIRCULATION PUMP WILL BE PROTECTED AGAINST THE |
| OUTDOOR ELEMENTS. |
| 4- MASTER BATH TUB REQUIRES A CONTROL VALVE BY A WATER |
| TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE 1070 |
| OR CSA B125.3, EXCEPT WHERE SUCH PROTECTION IS |
| OTHERWISE PROVIDED BY A COMBINATION TUB/SHOWER VALVE IN |
| ACCORDANCE WITH SECTION P2708.4. FBC R 2713.3 BATHTUB |
| AND WHIRLPOOL BATHTUB VALVES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |