2021-04-19 21:14:561ST REVIEW FBC-2020 PLUMBING
 PERMIT-21031623
 4/19/2021
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020
 FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH
 EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1- PLEASE INDICATE ON THE PLANS IN ALL AREAS THE MOST
 CURRENT CODE CYCLE. THE CURRENT CODE CYCLE IS FBC 2020
 2- ON PLAN PAGE P3 WATER HEATER NOTE: THERMAL EXPANSION
 IS REQUIRED PER FBC 2020 SEC.607.3THERMAL EXPANSION
 CONTROL.
 WHERE A STORAGE WATER HEATER IS SUPPLIED WITH COLD
 WATER THAT PASSES THROUGH A CHECK VALVE, PRESSURE
 REDUCING VALVE OR BACKFLOW PREVENTER, A THERMAL
 EXPANSION CONTROL DEVICE SHALL BE CONNECTED TO THE
 WATER HEATER COLD WATER SUPPLY PIPE AT A POINT THAT IS
 DOWNSTREAM OF ALL CHECK VALVES, PRESSURE REDUCING
 VALVES AND BACKFLOW PREVENTERS. THERMAL EXPANSION
 CONTROL DEVICES SHALL BE SIZED IN ACCORDANCE WITH THE
 MANUFACTURER?S INSTRUCTIONS AND SHALL BE SIZED SUCH
 THAT THE PRESSURE IN THE WATER DISTRIBUTION SYSTEM
 SHALL NOT EXCEED THAT REQUIRED BY SECTION 604.8.
 3- IT APPEARS AS THOUGH THE HEAT RECIRCULATION PUMP
 WILL BE INSTALLED OUTDOORS? PLEASE INDICATE HOW THE
 RECIRCULATION PUMP WILL BE PROTECTED AGAINST THE
 OUTDOOR ELEMENTS.
 4- MASTER BATH TUB REQUIRES A CONTROL VALVE BY A WATER
 TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE 1070
 OR CSA B125.3, EXCEPT WHERE SUCH PROTECTION IS
 OTHERWISE PROVIDED BY A COMBINATION TUB/SHOWER VALVE IN
 ACCORDANCE WITH SECTION P2708.4. FBC R 2713.3 BATHTUB
 AND WHIRLPOOL BATHTUB VALVES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  