Plan Review Notes
Plan Review Notes For Permit 21031623
Permit Number 21031623
Review Stop G
Sequence Number 1
Notes
Date Text
2021-04-19 20:49:321ST REVIEW FBC-2020 GAS
 PERMIT-21031623
 4/19/2021
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020
 FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH
 EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1- PLEASE INDICATE ON THE PLANS IN ALL AREAS THE MOST
 CURRENT CODE CYCLE. THE CURRENT CODE CYCLE IS FBC 2020
 2- SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2020
 FBC FUEL GAS SEC. 304.1, 614.5 (CLOTHES DRYERS) OR 2020
 FBC FUEL GAS RES. SEC. G2407.1 AND G2439.4 (CLOTHES
 DRYERS).
 3- SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2020 FBC FUEL GAS SEC.410.1 OR 2020 FBC
 FUEL GAS RES. SEC. G2421.1.
 4- 2ND STAGE REGULATORS REQUIRED ON TANKLESS WATER
 HEATERS PER MANUFACTURES MAX GAS INLET PRESSURE
 5- ON PLAN PAGE P2 COMENT IN CENTER OF GAS RISER: UNDER
 CONCRETE SLAB SCH 40 METALIC PIPE SHALL BE REMOVED FROM
 THE PLAN PER FBC FG 2020 SEC.404.14PIPING UNDERGROUND
 BENEATH BUILDINGS.
 PIPING INSTALLED UNDERGROUND BENEATH BUILDINGS IS
 PROHIBITED
 6- SUBMIT COMPLETE MANUFACTURER'S SPECIFICATIONS FOR
 THE GAS DRYER. THE GAS DRYER SHALL BE LISTED AND
 LABELED PER THE 2020 FBC FUEL GAS SEC.301.3 OR 2020 FBC
 FUEL GAS RES. SEC. G2404.3. THE MANUFACTURER'S
 SPECIFICATIONS SHALL NOTE THE CFM'S THAT ARE BEING
 EXHAUSTED BY THE DRYER.
 7- A GAS GRILL IS LABELED FOR OUTSIDE USE AND IT SEEMS
 TO BE IN A COVERED PATIO, IF SO PLEASE PROVIDE
 MANUFACTURES RECOMMENDATION FOR A VENTILATION HOOD,
 2020 FBC FG SEC.G2408.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  
  
  