2021-05-03 16:19:05 | 05/03/21 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF |
| THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH |
| FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA |
| STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC. |
| 107.1 GENERAL. |
| |
| 2. SUBMIT MANUFACTURER'S SPECIFICATION |
| SHEETS/INSTALLATION MANUAL FOR THE FIRE PIT TO VERIFY |
| COMPLIANCE WITH 2020 FBC RES. SEC. G2408.1. |
| |
| 3. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2020 |
| FBC RES. SEC. G2413.2 AND G2404.3. |
| |
| 4. THE ORIGINAL GAS PLAN WAS SUBMITTED BY AN ARCHITECT, |
| AND THE REVISION IS SUBMITTED BY A GAS CONTRACTOR. IF |
| THE GAS CONTRACTOR IS TAKING OVER PLEASE HAVE |
| ADMINISTRATIVE DOCUMENTATION PROVIDED FOR THE CHANGE |
| PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 5. PLEASE PROVIDE A GAS RISER DIAGRAM PER THE WPB |
| AMENDMENTS TO THE FBC SEC. 107.3.5.3 (13) RESIDENTIAL |
| GAS. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |