2022-01-11 13:56:19 | 4TH REVIEW FBC-2017 PLUMBING |
| PERMIT- 21031564 (REVISION TO 20100237) |
| 1/11/22 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. THIS IS THE 4TH FAILED |
| REVIEW OF THE PLUMBING PLANS FOR THE PROJECT. NO |
| NARRATIVE WAS PROVIDED IN RESPONSE TO THE 3RD REVIEW |
| COMMENT WHICH IS LISTED BELOW. PLEASE HAVE THE |
| ARCHITECT REVIEW SECS. 212.3, 213.2 & 213.3 FBC ACC AND |
| RESPOND TO THE COMMENTS OR CONTACT ME FOR FURTHER |
| INFORMATION. |
| |
| 1) SHEETS A1 & A2: AS NOTED ON SHEET A1 UNDER CODE DATA |
| THE PRIVATE BATHROOM SHALL BE DESIGNED AND CONSTRUCTED |
| IN COMPLIANCE WITH THE FBC ACC- 2017. PLEASE ADDRESS |
| THE FOLLOWING CODE REQUIREMENTS ITEMIZED BELOW AND NOTE |
| THAT THERE ARE NO EXCEPTIONS IN THE CODES LISTED THAT |
| EXEMPTS PRIVATE OFFICES. |
| A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| WATER CLOSET- SECTION 604.3. |
| B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| LAVATORY- SECTION 606.2. (NOTE- ITEM 1 EXEMPTS THE KNEE |
| AND TOE CLEARANCES.) |
| C) TURNING SPACE DIAGRAM AND DIAMETER- SECTION 304.3. |
| D) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL- |
| SECTION 604.2. |
| E) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE |
| REFLECTIVE SURFACE- SECTION 603.3 |
| F) WATER CLOSET GRAB BAR REINFORCEMENT LOCATIONS BASED |
| ON SECTIONS 604.5 & 609.4. |
| G) LOCATION OF THE WATER CLOSET FLUSH CONTROL- SECTION |
| 604.6. |
| H) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED |
| FROM THE FRONT OF THE WATER CLOSET- SECTION AND FIGURE |
| 604.7. |
| I) BASED ON SECTIONS 608.2 THE SHOWER COMPARTMENT SHALL |
| BE EITHER BE A TRANSFER TYPE DIMENSIONED AT 36X36 |
| INCHES, OR A STANDARD ROLL-IN TYPE WITH MINIMUM CLEAR |
| DIMENSIONS OF 30X60 INCHES. |
| K) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR EITHER |
| A TRANSFER OR ROLL-IN TYPE SHOWER- SECTIONS 608.2.1 & |
| 608.2.2.1. |
| L) SHOWER GRAB BAR REINFORCEMENT LOCATIONS BASED ON |
| SECTIONS 608.3 AND 609.4. |
| M) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE |
| SHOWER- SECTION 608.5.1 OR 608.5.2. |
| N) HEIGHT OF THE KITCHEN SINK- SECTION 606.3. (THE PLAN |
| SHOWS 36-INCHES HOWEVER THE CODE DOES NOT PROVIDE AN |
| EXCEPTION FOR KITCHEN SINKS FROM MEETING THE MAXIMUM |
| 34-INCHES FROM THE FINISH FLOOR TO THE HIGHER OF THE |
| RIM OF THE SINK OR COUNTER SURFACE). |
| O) CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR THE |
| KITCHEN SINK- SECTION 606.2. (ITEM 1 ALLOWS FOR A |
| PARALLEL APPROACH BECAUSE THERE IS NO COOKTOP OR |
| RANGE). |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |