Plan Review Notes For Permit 21031564 |
Permit Number |
21031564 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2022-01-18 09:38:07 | REVISION CREATING OFFICE FROM WAREHOUSE | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) PLEASE SHOW THE ACCESSIBLE DETAILS FOR THE RESTROOM | | - CLEAR FLOOR SPACE FOR FIXTURES, GRAB BAR LOCATIONS, | | TOILET PAPER HOLDER LOCATIONS, MIRROR LOCATIONS, ETC | | PER FBC ACCESSIBILITY CHAPTER 6 | | | | 2) RESTROOM DOOR DOES NOT HAVE A CLEAR WIDTH OF 32" PER | | FBC ACCESSIBILITY 404.2.3 CLEAR WIDTH. | | DOOR OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES | | (815 MM) MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH | | SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF | | THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES. | | | | | | | | |
|