Notes |
Date |
Text |
2021-10-21 09:11:40 | REVISION CREATING OFFICE FROM WAREHOUSE | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) OCCUPANCY CHANGE FROM WAREHOUSE STORAGE TO OFFICE | | "B" - THE LANDING AT THE ADDED EXTERIOR DOORS NEEDS TO | | BE EXTENDED (44" OUT FROM THE DOOR) TO COMPLY WITH FBC | | 1010.1.6 | | | | 2) PLEASE SHOW THE HEIGHT FROM THE FINISHED FLOOR TO | | THE BOTTOM OF THE CEILING DECK ADDED IN FRONT OF THE | | NEW DOOR. FBC 1208.2 | | | | 3) PLEASE SHOW THE ACCESSIBLE DETAILS FOR THE RESTROOM | | - CLEAR FLOOR SPACE FOR FIXTURES, GRAB BAR LOCATIONS, | | TOILET PAPER HOLDER LOCATIONS, MIRROR LOCATIONS, ETC | | PER FBC ACCESSIBILITY CHAPTER 6 | | | | 4) RESTROOM DOOR DOES NOT HAVE A CLEAR WIDTH OF 32" PER | | FBC ACCESSIBILITY 404.2.3 CLEAR WIDTH. | | DOOR OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES | | (815 MM) MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH | | SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF | | THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES. | | | | | | | | |
|