2021-06-03 11:13:39 | 2ND REVIEW FBC-2017 PLUMBING |
| PERMIT- 21031564 (REVISION TO 20100237) |
| 6/3/2021 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE REVISED PLAN INDICATES A CHANGE OF OCCUPANCY |
| FROM AN S TO A B OCCUPANCY- STORAGE WAREHOUSE TO |
| PRIVATE OFFICE. BASED ON THE PLAN THIS APPEARS TO BE A |
| NEW TENANT OCCUPANCY. REFER TO SECTIONS 202, AND 1010.1 |
| FBC EX AND PROVIDE PLUMBING FIXTURE CALCULATIONS FOR |
| THE B OCCUPANCY IN ACCORDANCE WITH TABLE 403.1 FBC P. |
| PLEASE NOTE THAT THE PLAN DOES NOT PROVIDE AN OCCUPANCY |
| CLASSIFICATION OR OCCUPANT LOAD, HOWEVER IT APPEARS |
| THAT AT A MINIMUM ONE ACCESSIBLE TOILET ROOM FOR BOTH |
| MALE AND FEMALE USE WOULD BE REQUIRED PER TABLE 403.1, |
| AND THE APPLICABLE SUB- SECTIONS UNDER 403. THE |
| PREVIOUS PLAN INDICATED A NEW TOILET ROOM HOWEVER THE |
| REQUIRED TOILET ROOM AND REQUIRED FIXTURES HAVE BEEN |
| ELIMINATED. PLEASE REVISE THE PLAN TO SHOW THE PLUMBING |
| PIPING AND ACCESSIBILITY DETAILS. |
| |
| 2) PLUMBING: |
| A) SANITARY AND WATER SUPPLY FLOOR PLAN DRAWINGS AND |
| RISERS. |
| B) PLUMBING FIXTURE SCHEDULE. |
| C) REQUIRED HOT WATER SOURCE AND SUPPLY FOR WASHING, |
| CULINARY PURPOSES, CLEANING ETC. |
| |
| 3) ACCESSIBILITY: |
| A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| WATER CLOSET- SECTION 604.3. |
| B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| LAVATORY- SECTION 606.2. |
| C) TURNING SPACE DIAGRAM AND DIAMETER- SECTION 304.3. |
| D) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL- |
| SECTION 604.2. |
| E) HEIGHT OF THE WATER CLOSET SEAT FROM THE FINISHED |
| FLOOR- SECTION 604.4. |
| F) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE |
| REFLECTIVE SURFACE- SECTION 603.3 |
| G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| BARS FOR THE WATER CLOSET- SECTION 604.5 & 609.4, |
| FIGURES 604. |
| H) LOCATION OF THE WATER CLOSET FLUSH CONTROL- SECTION |
| 604.6. |
| I) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED |
| FROM THE FRONT OF THE WATER CLOSET- SECTION AND FIGURE |
| 604.7. |
| K) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION |
| 606.2. |
| |
| 3) THE SUBMITTED ENERGY EFFICIENCY FORM R405 IS USED |
| FOR RESIDENTIAL OCCUPANCIES. PLEASE PROVIDE THE |
| APPLICABLE COMPLIANCE DOCUMENT- SECTION C101.5.1 FBC |
| EC. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |