Plan Review Notes
Plan Review Notes For Permit 21031564
Permit Number 21031564
Review Stop P
Sequence Number 2
Notes
Date Text
2021-06-03 11:13:392ND REVIEW FBC-2017 PLUMBING
 PERMIT- 21031564 (REVISION TO 20100237)
 6/3/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REVISED PLAN INDICATES A CHANGE OF OCCUPANCY
 FROM AN S TO A B OCCUPANCY- STORAGE WAREHOUSE TO
 PRIVATE OFFICE. BASED ON THE PLAN THIS APPEARS TO BE A
 NEW TENANT OCCUPANCY. REFER TO SECTIONS 202, AND 1010.1
 FBC EX AND PROVIDE PLUMBING FIXTURE CALCULATIONS FOR
 THE B OCCUPANCY IN ACCORDANCE WITH TABLE 403.1 FBC P.
 PLEASE NOTE THAT THE PLAN DOES NOT PROVIDE AN OCCUPANCY
 CLASSIFICATION OR OCCUPANT LOAD, HOWEVER IT APPEARS
 THAT AT A MINIMUM ONE ACCESSIBLE TOILET ROOM FOR BOTH
 MALE AND FEMALE USE WOULD BE REQUIRED PER TABLE 403.1,
 AND THE APPLICABLE SUB- SECTIONS UNDER 403. THE
 PREVIOUS PLAN INDICATED A NEW TOILET ROOM HOWEVER THE
 REQUIRED TOILET ROOM AND REQUIRED FIXTURES HAVE BEEN
 ELIMINATED. PLEASE REVISE THE PLAN TO SHOW THE PLUMBING
 PIPING AND ACCESSIBILITY DETAILS.
  
 2) PLUMBING:
 A) SANITARY AND WATER SUPPLY FLOOR PLAN DRAWINGS AND
 RISERS.
 B) PLUMBING FIXTURE SCHEDULE.
 C) REQUIRED HOT WATER SOURCE AND SUPPLY FOR WASHING,
 CULINARY PURPOSES, CLEANING ETC.
  
 3) ACCESSIBILITY:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSET- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORY- SECTION 606.2.
 C) TURNING SPACE DIAGRAM AND DIAMETER- SECTION 304.3.
 D) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL-
 SECTION 604.2.
 E) HEIGHT OF THE WATER CLOSET SEAT FROM THE FINISHED
 FLOOR- SECTION 604.4.
 F) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE
 REFLECTIVE SURFACE- SECTION 603.3
 G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSET- SECTION 604.5 & 609.4,
 FIGURES 604.
 H) LOCATION OF THE WATER CLOSET FLUSH CONTROL- SECTION
 604.6.
 I) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONT OF THE WATER CLOSET- SECTION AND FIGURE
 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION
 606.2.
  
 3) THE SUBMITTED ENERGY EFFICIENCY FORM R405 IS USED
 FOR RESIDENTIAL OCCUPANCIES. PLEASE PROVIDE THE
 APPLICABLE COMPLIANCE DOCUMENT- SECTION C101.5.1 FBC
 EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  