2021-05-28 10:54:06PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT A GENERATOR PAD DRAWING THAT SPECIFIES HOW
 THE GENERATOR IS ANCHORED TO RESIST WIND LOADS. IF YOU
 ARE USING A PREFABRICATED GENERATOR PAD SUBMIT THE
 SIGNED AND SEALED SITE SPECIFIC ENGINEERING FOR IT.
 SPECIFY THE WIND LOAD DATA ON THE DRAWING. FBC 107.2.1
  
 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE
 OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE
 OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048
 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS
 VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS,
 PARKING LOTS AND LOADING DOCKS.
  
 3) SEE SIGNATURE REVIEW.