Plan Review Notes For Permit 21031555 |
Permit Number |
21031555 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-05-28 10:54:06 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT A GENERATOR PAD DRAWING THAT SPECIFIES HOW | | THE GENERATOR IS ANCHORED TO RESIST WIND LOADS. IF YOU | | ARE USING A PREFABRICATED GENERATOR PAD SUBMIT THE | | SIGNED AND SEALED SITE SPECIFIC ENGINEERING FOR IT. | | SPECIFY THE WIND LOAD DATA ON THE DRAWING. FBC 107.2.1 | | | | 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10 | | FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE | | OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE | | OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 | | MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS | | VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, | | PARKING LOTS AND LOADING DOCKS. | | | | 3) SEE SIGNATURE REVIEW. |
|