Plan Review Notes For Permit 21031545 |
Permit Number |
21031545 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-04-16 13:35:42 | PLAN REVIEW ELECTRIC | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER PX3169 1&2 FAMILY - SFP306 | | INSPECTOR BN4338 | | BUILDING OFFICIAL BU1635 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CODES IN EFFECT: | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | 2017 NEC | | | | 1ST REVIEW | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. ELECTRICAL PERMIT REQIUIRED. | | PERMITS - 105.1 REQUIRED. | | | | 2. PROVIDE AN ELECTRICAL PLAN. IDENTIFY ANY NEW CIRCUTS | | AND WHAT BRANCH CIRCUT THEY ARE CONNECTED TO. | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | 107.2.5. | | | | 3. PROVIDE AN UPDATED PANEL SCHEDULE. | | PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY | | WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, | | 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | |
|