Plan Review Notes For Permit 21031501
Permit Number 21031501
Review Stop B
Sequence Number 2
Notes
Date Text
2021-05-24 15:47:05COMMERCIAL ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWING A0.0 IN "PROJECT DATA" THE COMMON CORRIDOR
 IS SHOWN AS NON RATED - AFTER REVIEWING PAST PERMITS
 FOR THE BUILDING IT HAS BEEN DETERMINED THAT THE
 EXISTING COMMON CORRIDOR HAS A 1 HOUR FIRE RATING.
 PLEASE SHOW THE HOURLY FIRE RATING FOR THE COMMON
 CORRIDOR. (IF THE ELEVATOR HOISTWAY IS PRESSURIZED
 PLEASE SHOW IN WRITING ON THE DRAWINGS)
 2) PLEASE SHOW THE HOURLY FIRE RATING FOR THE ADDED
 DOOR PER FBC 716.5
 3) PLEASE SHOW DOOR TO BE SELF CLOSING AND LATCHING PER
 FBC 716.5.9
  
  