Plan Review Notes
Plan Review Notes For Permit 21031479
Permit Number 21031479
Review Stop P
Sequence Number 1
Notes
Date Text
2021-05-03 05:46:221) PROVIDE A SITE PLAN SHOWING THE LOCATION OF THE
 GREASE INTERCEPTORS. WPB AMEND. TO FBC SEC. 107.2.1.
 2) THE CONCRETE GREASE INTERCEPTOR SHALL COMPLY WITH
 CITY STANDARD DETAIL DRAWING GS-7. THE DETAIL PROVIDED
 IS FOR PALM BEACH COUNTY.PLEASE CONTACT THE CITY OF
 WEST PALM BEACH ENGINEERING DEPARTMENT AT 561-835-7423
 FOR A COPY OF DETAIL GS-7.
 3) A SAMPLING PORT IS REQUIRED ON THE DISCHARGE LINE
 FROM THE INTERCEPTORS PRIOR TO THE CONNECTION TO THE
 SANITARY SEWER.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  