Plan Review Notes
Plan Review Notes For Permit 21031467
Permit Number 21031467
Review Stop B
Sequence Number 3
Notes
Date Text
2021-06-14 12:49:52DAYCARE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) FBC 466.8 CORRIDORS. IN BUILDINGS PROTECTED
 THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH SECTIONS 901.6 AND
 903.3.1.1 CORRIDOR WALLS SHALL NOT BE REQUIRED TO BE
 RATED, PROVIDED THAT SUCH WALLS FORM SMOKE PARTITIONS
 IN ACCORDANCE WITH SECTION 710.
 2) PLEASE SHOW THAT THE EXISTING CORRIDOR WALLS MEET
 THE REQUIREMENTS OF SMOKE PARTITIONS - FBC 710.4
 CONTINUITY.
 SMOKE PARTITIONS SHALL EXTEND FROM THE TOP OF THE
 FOUNDATION OR FLOOR BELOW TO THE UNDERSIDE OF THE FLOOR
 OR ROOF SHEATHING, DECK OR SLAB ABOVE OR TO THE
 UNDERSIDE OF THE CEILING ABOVE WHERE THE CEILING
 MEMBRANE IS CONSTRUCTED TO LIMIT THE TRANSFER OF SMOKE.
 3) RESTROOMS FOR AGE GROUP 3 & 4 = ADA RESTROOM PAPER
 TOWEL DISPENSER - THE OUTLET OF THE DISPENSER SHOULD BE
 SHOWN TO MEET THE REACH RANGES SEE FBC ACCESSIBILITY
 308.1 (SEE ALSO THE ADVISORY FOR AGE GROUPS) - DRAWING
 P-1 "RESTROOM REFERENCE NOTES" NOTE NUMBER 1 SHOWS THE
 LOW REACH AT 15" - SHOULD BE 20". - THIS SHOULD ALSO BE
 SHOWN ON DRAWING A-1
 4) PRODUCT APPROVAL (FL14237-R3) FOR THE EXTERIOR DOOR
 HAS EXPIRED - PLEASE PROVIDE THE UPDATED VERSION
 (FL14237-R5) FRONT PAGES AND THE INSTALLATION
 INSTRUCTIONS. DOOR PRODUCT APPROVAL NEEDS TO BE
 REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD
 OR BE LISTED BY PRODUCT APPROVAL NUMBER ON THE
 DRAWINGS.
 5) PLEASE SHOW THAT CLOSURES ARE REQUIRED FOR THE EXIT
 DOORS - FBC 466.4 DOOR CLOSURE.
 ANY EXIT DOOR DESIGNED TO BE NORMALLY CLOSED SHALL BE
 KEPT CLOSED AND SHALL COMPLY WITH SECTION 716.5.
 6) PLEASE SHOW WALL FINISH AT THE MOP SINK TO COMPLY
 WITH FBC 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE. (DRYWALL IS NOT CONSIDERED A HARD SURFACE)
  
  