2021-05-25 18:20:232ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21031467
 5/25/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS FROM THE 1ST
 REVIEW LISTED BELOW HAVE BEEN MARKED AS PASSED OR
 FAILED. NOTES IN CAPS HAVE BEEN ADDED TO FAILED
 COMMENTS FOR FURTHER CLARIFICATION. PLEASE NOTE THAT I
 AM AVAILABLE TO DISCUSS ANY OF THE COMMENTS WITH THE
 DESIGN PROFESSIONALS AND THE CONTRACTOR TO HELP
 EXPEDITE APPROVAL OF THE PLUMBING PLANS.
  
 1) FAILED. SHEETS CS-1, A-1 & P-1: CONCERNING TOILET RM
 113 PLEASE REFER TO SECTION 213.2 EXCEPTION-3 AND THE
 ADVISORY UNDER THE SECTION- ADVISORY 213.2 TOILET ROOMS
 AND BATHING ROOMS EXCEPTIONS 3 AND 4. A "CLUSTER" IS A
 GROUP OF TOILET ROOMS PROXIMATE TO ONE ANOTHER.
 GENERALLY, TOILET ROOMS IN A CLUSTER ARE WITHIN SIGHT
 OF, OR ADJACENT TO, ONE ANOTHER. TOILET RM 113 DOES NOT
 MEET THE EXCEPTION AND SHALL BE DESIGNED TO BE
 ACCESSIBLE IN ACCORDANCE WITH SECTIONS 213.2 AND 603.
 BASED ON TABLE 403.3 AND SECTIONS 403.2 & 403.3 IT
 APPEARS THAT A REQUIRED PUBLIC/EMPLOYEE TOILET ROOM HAS
 BEEN ELIMINATED. THE PREVIOUS PLAN SHOWED THE
 CHILDREN'S SEPARATED BOYS AND GIRLS TOILET ROOMS AND
 ALSO TOILET ROOMS- 108 & 113. THE TWO UNISEX TOILET
 ROOMS APPEARED TO MEET THE REQUIREMENT FOR SEPARATE
 FACILITIES FOR THE PUBLIC AND EMPLOYEES- SECTION 403.3.
 AND ALSO MATCHED THE FIXTURE CALCULATION TABLE ON CS-1
 WHICH INDICATED TWO UNISEX TOILET ROOMS. TOILET ROOM
 113 IS NOW CONVERTED INTO CLOSET 113, AND THE PLUMBING
 FIXTURE CALCULATIONS ON CS-1 HAVE BEEN REVISED TO SHOW
 ONE UNISEX TOILET ROOM. PLEASE REVISE THE PLAN TO SHOW
 THE TWO REQUIRED TOILET ROOMS.
  
 2) FAILED. SHEETS A-1 & P-1: REFER TO SECTION 403.2 FBC
 P AND LABEL TOILET RM 113 AS EITHER MALE OR FEMALE.
 REFER TO ABOVE NOTES ON COMMENT #1. SEPARATE FACILTIES
 ARE REQUIRED HOWEVER IT IS ACCEPTABLE TO LABEL BOTH
 TOILET ROOMS AS UNISEX BASED ON SECTION 403.2.1 FBC P.
 PLEASE REVISE THE PLAN TO SHOW THE LOCATIONS OF THE
 REQUIRED PUBLIC/EMPLOYEE TOILET ROOMS.
  
 ***ADVISORY FOR COMMENTS #1 & 2: THE CURRENT PLAN SHOWS
 COMPLIANCE FOR THE NUMBER OF REQUIRED ACCESSIBLE
 FIXTURES FOR THE BOYS AND GIRLS- TOILET RMS-109 AND
 112. THE FIXTURES IN GIRLS-RM 110 ARE NOT REQUIRED
 WHICH PROVIDES AN OPTION OF REDESIGNING THE ROOM TO
 MEET THE REQUIREMENT FOR THE MISSING ACCESSIBLE
 PUBLIC/EMPLOYEE TOILET ROOM FIXTURES.
  
 3) PASSED. SHEETS A-1 & P-1: REFER TO SECTIONS 604.1,
 604.9, AND ADVISORY 604.9 AND SPECIFICATIONS TABLE-
 "ADVISORY 604.9 WATER CLOSETS AND TOILET COMPARTMENTS
 FOR CHILDREN'S USE. THE REQUIREMENTS IN 604.9 ARE TO BE
 FOLLOWED WHERE THE EXCEPTION FOR CHILDREN'S WATER
 CLOSETS IN 604.1 IS USED. THE FOLLOWING TABLE PROVIDES
 ADDITIONAL GUIDANCE IN APPLYING THE SPECIFICATIONS FOR
 WATER CLOSETS FOR CHILDREN ACCORDING TO THE AGE GROUP
 SERVED AND REFLECTS THE DIFFERENCES IN THE SIZE,
 STATURE, AND REACH RANGES OF CHILDREN AGES 3 THROUGH
 12. THE SPECIFICATIONS CHOSEN SHOULD CORRESPOND TO THE
 AGE OF THE PRIMARY USER GROUP. THE SPECIFICATIONS OF
 ONE AGE GROUP SHOULD BE APPLIED CONSISTENTLY IN THE
 INSTALLATION OF A WATER CLOSET AND RELATED ELEMENTS."
 PLEASE REVISE THE FLOOR PLAN AND ELEVATION DRAWINGS ON
 A-1 TO SHOW THE AGE DESIGNATION FOR EACH TOILET ROOM.
  
 4) PASSED. A-1: PROVIDE THE SPOUT HEIGHT FOR THE HIGH-
 STANDING PERSONS DRINKING FOUNTAIN- SECTION 602.7.
 REFER TO FIGURE 602.5 AND SHOW SPOUT LOCATIONS.
  
 5) PASSED. A-1: REFER TO SECTION AND SHOW HOW THE
 LOCATIONS OF THE FOUNTAINS WILL BE IN COMPLIANCE WITH
 SECTION 307.2 PROTRUSION LIMITS.
  
 6) PASSED. P-1: PROVIDE A PLUMBING FIXTURE SCHEDULE IN
 COMPLIANCE WITH SECTION 405 FBC P.
  
 7) FAILED. P-1 PLUMBING PLAN AND SANITARY RISER- FBC P:
 THE EWC IS NOT LABELED IN THE RISER.
  
 A) FAILED. THE 1-1/4 IN. TRAP FOR THE URINAL CANNOT BE
 APPROVED WITHOUT SUBMITTAL OF URINAL SPECIFICATIONS IN
 THE REQUESTED FIXTURE SCHEDULE- TABLE 709.1. THE
 COMMENT RESPONSE FROM THE ARCHITECT INDICATES THE
 URINAL WILL HAVE A 2 INCH TRAP HOWEVER AN 1-1/4 INCH
 TRAP IS SHOWN.
  
 B) PASSED. SHOW THE REQUIRED CLEANOUT AT THE JUNCTION
 OF THE BUILDING DRAIN AND SEWER- SECTION 708.1.3.
  
 C) PASSED. PROVIDE A VENT FOR THE WATER CLOSET IN 112-
 SECTION 901.2.1.
  
 D) PASSED. PROVIDE AN INDIVIDUAL VENT FOR THE URINAL IN
 112- SECTIONS 911.1 & 912.1.
  
 E) PASSED. THE WYE FITTING BY THE WATER CLOSET IN GIRLS
 110 IS NOT PROPERLY DIRECTING THE FLOW OF DRAINAGE FROM
 THE WATER CLOSET AND THE DRAIN PIPE FROM TOILET RM 113-
 SECTION 706.3.
  
 F) PASSED. PROVIDE THE SIZE OF THE TRAPS AT THE
 3-COMPARTMENT SINK- TABLE 709.1. PLEASE NOTE EACH WELL
 OF A MULTIPLE-COMPARTMENT SINK SHALL DISCHARGE
 INDEPENDENTLY TO A WASTE RECEPTOR- SECTION 802.1.1.
 PROVIDE A DETAIL AND INDICATE WHICH TYPE OF INDIRECT
 WASTE RECEPTOR WILL BE INSTALLED AND ADD IT TO THE
 FIXTURE SCHEDULE- SECTION 802.4 FBC P.
  
 8) FAILED. P1: PLEASE PROVIDE THE SIZES OF ALL SUPPLY
 PIPES SHOWN IN THE WATER RISER- TABLE 604.5 FBC P.
 PLEASE SHOW A 3/4 INCH SUPPLY LINE TO THE URINAL PER
 THE SLOAN 186- XL-1 FLUSHOMETER SPECIFICATIONS.
  
 9) PASSED. P1: INDICATE HOW TEMPERED WATER WILL BE
 PROVIDE AT THE LAVATORIES- SECTION 419.5 AND 607.2.1
 FBC P.
  
 10) PASSED. P1: THE MAXIMUM ALLOWABLE PIPING LENGTH
 FROM THE NEAREST SOURCE OF HEATED WATER TO THE
 TERMINATION OF THE LAVATORY SUPPLY PIPES SHALL BE IN
 ACCORDANCE WITH SECTION C404.5.1 & TABLE C404.5.1 FBC
 EC.
  
 11) PASSED. P1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE
 WATER HEATER INDICATING THE MAKE, MODEL, KW SIZE, AND
 EFFICIENCY RATING OF THE UNIT- TABLE C404.2 FBC EC.
 SUBMIT MANUFACTURER'S SPECIFICATIONS.
  
 12) PASSED. P1: PROVIDE A PIPING DIAGRAM FOR THE WATER
 HEATER- SECTION 502.1 FBC P.
  
 13) PASSED.P1: SHOW LOCATIONS OF REQUIRED WATER HAMMER
 ARRESTORS AND PROVIDE A DEVICE SCHEDULE- SECTION 604.9
 FBC P.
  
 14) PASSED. P1: REFER TO TABLE C403.2.10 FBC EC AND
 PROVIDE THE THICKNESSES OF THE HOT WATER PIPE
 INSULATION.
  
 NEW COMMENTS BASED ON REVISED PLANS.
  
 P1 RESTROOM REFERENCE NOTES: PLEASE REMOVE RM 113
 REFERENCES IN THE SCHEDULE. RM 113 HAS BEEN CONVERTED
 TO A CLOSET. A) REMOVE OR REVISE NOTE 7 FROM RM 109. B)
 NOTE 4 HAS BEEN USED TWICE. C) THE TEXT FOR NOTE 5 IS
 NOT PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  